W-Modbus Solar Kit (840-2102) customer Q&A
Every answer on this page applies only to the W-Modbus Solar Kit (SKU 840-2102, Modbus RTU). Do not use these answers for other LumenRadio products or form factors. Full manual: W-Modbus Solar Kit manual
Product overview
W-Modbus Solar Kit (840-2102): What is the W-Modbus Solar Kit and what does it do?
Also asked as:
- What is the W-Modbus Solar Kit used for?
- Can you give me an overview of the Solar Kit?
- How does the Solar Kit work?
The Solar Kit is two pre-paired, pre-configured W-Modbus DIN rail units, labelled GATEWAY and NODE. They replace the RS485 cable between a solar inverter and its smart meter with a wireless link. Solar Mode is enabled from the factory to handle the very fast poll rates of solar inverters, and no commissioning is needed out of the box.
Manual section: Setup Guide; Application Guide (section ID: product-overview)
W-Modbus Solar Kit (840-2102): When should I use the Solar Kit?
Also asked as:
- Is the Solar Kit right for my solar installation?
- Why would I use the Solar Kit instead of a cable?
- What problems does the Solar Kit solve?
Use it when the inverter and smart meter are physically separated and a wired RS485 run is impractical, when the inverter polls the meter very fast (response window of 100 ms or less), and when you want a plug-and-play wireless replacement that needs no commissioning out of the box.
Manual section: Application Guide > When to use the Solar Kit (section ID: when-to-use-the-solar-kit)
W-Modbus Solar Kit (840-2102): How many devices can a W-Modbus network support?
Also asked as:
- What is the maximum number of nodes in a W-Modbus network?
- How many devices can I connect to one gateway?
- Is there a limit on network size?
Out of the box the kit is one gateway and one node: the GATEWAY connects to the inverter (the Modbus RTU client) and the NODE to the smart meter. You can add repeater nodes if the link is weak. A W-Modbus network supports up to 100 mesh nodes per gateway; each DIN rail node supports 1 local Modbus RTU device.
W-Modbus Solar Kit (840-2102): What is included in the Solar Kit?
Also asked as:
- What comes in the Solar Kit box?
- What are the kit contents?
- Does the kit include power supplies and antennas?
2× W-Modbus DIN rail units (pre-configured as GATEWAY and NODE), 2× 24 VDC power supplies, 2× 1.8 dBi outdoor antennas and 2× RP-SMA to N-type connector cables.
Manual section: Setup Guide > Kit contents (section ID: kit-contents)
W-Modbus Solar Kit (840-2102): What is the difference between a Gateway and a Node?
Also asked as:
- Should my device be a gateway or a node?
- What role does the gateway play compared to a node?
- Where do I connect the controller – to the gateway or a node?
The Gateway is the central root device of the network, and all wireless unicast messages pass through it. The Modbus RTU client (master) must be connected to the Gateway – in the Solar Kit that is the inverter, so the unit labelled GATEWAY goes at the inverter and the NODE at the smart meter. Every node also acts as a repeater automatically, even with no Modbus device connected. Use only one Gateway per network.
Manual section: Glossary of Terms; System Description > W-Modbus Mesh Network; Radio planning > Gateway & Node selection (section ID: gateway-node-selection)
Safety
W-Modbus Solar Kit (840-2102): What safety precautions apply when installing the device?
Also asked as:
- Are there any safety warnings for installation?
- What do I need to know about electrical safety?
- Who is allowed to install the device?
Disconnect power before wiring, verify the supply matches spec and check DC polarity, use correctly rated wiring and overcurrent protection, follow local electrical codes, use ESD protection, and have only qualified technicians install it. Do not install in wet locations or above 95% RH, do not use if damaged, and do not use for safety-critical tasks.
Manual section: Safety Information; Warnings and Precautions (section ID: safety-information)
W-Modbus Solar Kit (840-2102): What should I watch out for when sharing a power supply with other devices?
Also asked as:
- Can I use the same transformer for this device and other equipment?
- Can I share a 24 VAC transformer with other devices?
- What is the half-wave rectified circuit caution?
W-Modbus uses a half-wave rectified circuit, so it should not share a VAC transformer with a device that uses a full-wave rectified circuit. A shared transformer is only acceptable if the other devices are also half-wave rectified and all power connections have the same polarity: the W-Modbus "+" terminal must never be connected to the "–" terminal of another device. When connecting a 24 V isolation transformer, follow IEC 61558-1.
Manual section: Safety Information > Electrical Safety / Power and RS485 Circuit Caution (section ID: power-and-rs485-circuit-caution)
Specifications
W-Modbus Solar Kit (840-2102): What are the power requirements?
Also asked as:
- What voltage does the device need?
- Can I power it with 12 V or 24 V, AC or DC?
- How much power does the device consume?
Each unit is powered by the 24 VDC power supply included in the kit. The DIN rail units also accept 24 VAC ±10% or 12–24 VDC ±10%. Maximum consumption is 0.5 W (average 0.25 W); troubleshooting guidance asks for a supply that can deliver at least 0.5 A.
Manual section: Device Overview > Specifications; Troubleshooting > None of the LEDs are blinking (section ID: specifications)
W-Modbus Solar Kit (840-2102): What are the physical and environmental specs of the Solar Kit units?
Also asked as:
- What are the dimensions and weight of the Solar Kit units?
- What temperature and humidity range are the Solar Kit units rated for?
- What IP rating do the Solar Kit units have?
Each unit is a W-Modbus DIN rail: 36 × 93 × 59 mm, 87 g, IP20. Operating temperature −20 °C to +55 °C (−4 °F to 131 °F), storage −30 °C to +80 °C, humidity 10–95% non-condensing. Terminals accept 0.2–1.5 mm² conductors (AWG 24–16). Use a suitably rated enclosure outdoors.
Manual section: Device Overview > Specifications (section ID: specifications)
W-Modbus Solar Kit (840-2102): What radio frequency and output power does it use?
Also asked as:
- What frequency band does it operate on?
- What is the maximum transmit power?
- Does it use 2.4 GHz?
2402–2480 MHz (2.4 GHz band) with maximum RF output power of 100 mW. Network traffic is encrypted with AES-128 using credentials unique to each gateway.
Manual section: Device Overview > Specifications; System Description > W-Modbus Mesh Network (section ID: specifications)
W-Modbus Solar Kit (840-2102): Do the Solar Kit units have a termination resistor, and can I disable it?
Also asked as:
- Do the Solar Kit units have a built-in EOL resistor?
- Can I turn off the 120 Ω termination?
- Where should the units be placed on the RS485 line?
Yes, it has a built-in 120 Ω end-of-line resistor that cannot be disabled. Place the unit at one end of the RS485 trunk and terminate the other end with a 120 Ω resistor (built-in or external).
Device overview
W-Modbus Solar Kit (840-2102): What are the physical components on the device?
Also asked as:
- What are the parts on the device?
- What connectors and switches does the device have?
- Can you describe the device layout?
From the device overview: LEDs, RS485 bus-settings DIP switch, push button, 3-way mode switch, power connector, RS485 bus connector, antenna connector, DIN-rail clip, and a backplane connector (not in use).
Manual section: Device Overview (section ID: device-overview)
System
W-Modbus Solar Kit (840-2102): What is the difference between commissioning mode and secure mode?
Also asked as:
- What does commissioning mode mean?
- What is secure mode?
- When does the network switch from commissioning to secure mode?
Commissioning mode uses known, shared credentials so new nodes can find and join a gateway. When the gateway is switched to secure mode, all nodes reboot together and switch to encrypted credentials unique to that gateway for long-term operation, so nearby networks don't interfere.
Manual section: System Description > Commissioning Network / Secure Network (section ID: commissioning-network)
W-Modbus Solar Kit (840-2102): How does the gateway share its serial settings with nodes?
Also asked as:
- Do nodes use the gateway's baud rate?
- What is config distribution?
- Can a node use its own serial settings instead of the gateway's?
The gateway distributes its bus settings (baud rate, parity and stop bits) to all nodes. Wall mount and DIN rail nodes use the gateway configuration unless DIP switch 5 (use local serial configuration) is ON. Compact nodes always take their settings from the gateway. As long as Wall mounts and DIN rails are used as nodes, different baud rates can be mixed in one system.
Manual section: System Description > Config Distribution; Setup Guide > Set the baud rate on the Gateway (section ID: config-distribution)
W-Modbus Solar Kit (840-2102): What is FOTA and do I need to update every node?
Also asked as:
- How do firmware updates reach the nodes?
- Do I have to update each node separately?
- What is firmware over the air?
Firmware-Over-The-Air (from FW 3.0.0) lets the gateway push new firmware to every node in a secure network automatically. Update only the gateway, preferably through the W-Modbus app; propagation typically takes 30 minutes to 2 hours depending on network size. Progress is shown via FOTA Status in the app. If the devices run firmware below 3.0.0, FOTA is not available and they must be updated using the nRF Connect update flow.
Manual section: System Description > FOTA; Mobile App > Complete update / FOTA status (section ID: firmware-over-the-air-fota)
Accessories
W-Modbus Solar Kit (840-2102): What accessories are available for the Solar Kit?
Also asked as:
- Which accessories can I buy for the Solar Kit?
- Can I get a different antenna for the Solar Kit?
- What add-ons are available for the Solar Kit?
The kit already includes antennas, cables and power supplies. Because the units are DIN rails, the DIN rail accessories also fit: outdoor kit (800-2324), IP67 enclosure (800-2322), antennas 3.5 dBi (104-1040), 5 dBi puck (104-1033), 6 dBi directional (104-1004), super low loss cable (800-9101), DIN rail power supply (103-1046), outer shell (800-2323) and RP-SMA to N-type bulkhead cables (102-2011 / 102-2012).
Manual section: DIN Rail Accessories > Available Accessories (section ID: available-accessories)
W-Modbus Solar Kit (840-2102): How do I install W-Modbus outdoors?
Also asked as:
- Can I use W-Modbus outside?
- Is there an outdoor kit?
- What enclosure do I need for an outdoor installation?
Use a correctly rated enclosure. The recommended route is the DIN Outdoor Kit (800-2324): IP67 enclosure, 24 VDC power supply, N-type connector, outdoor antenna and sheet-metal vandal cover. If using 24 VAC from the cabinet and no vandal cover, buy the IP67 enclosure and antenna separately. Mount antennas where snow can't cover them.
See also: Radiation pattern (section ID: radiation-pattern), Wireless best practices (section ID: installation-and-placement-of-wireless-devices-and-external-antennas)
W-Modbus Solar Kit (840-2102): Can I use a third-party antenna?
Also asked as:
- Can I use my own antenna?
- Which antennas are compatible?
- Can I replace the stock antenna with a different one?
Yes. The DIN rail has an RP-SMA connector and accepts any RP-SMA antenna with 50 Ω impedance and resonance of 2400–2483.5 MHz. Note that the FCC requires use with approved antennas only. LumenRadio's antennas are the 1.8 dBi outdoor antenna (104-1041), the 3.5 dBi outdoor antenna (104-1040), the 5 dBi puck antenna (104-1033) and the 6 dBi directional antenna (104-1004). Whichever antenna you use, look at its radiation pattern to choose one that suits your application; see Radio planning > Radiation pattern (section ID: radiation-pattern).
Manual section: DIN Rail Accessories > Antennas; Regulatory > FCC Information to User (section ID: antennas)
W-Modbus Solar Kit (840-2102): Which antenna setup should I choose?
Also asked as:
- Which antenna should I use for my installation?
- How do I pick the right antenna and cable?
- Which antenna option is best for a metal enclosure?
- Which antenna SKUs or part numbers do I need?
- How do I choose an antenna that suits my application?
There are four antenna options for the DIN rail. Option 1, external antenna (the standard choice when the unit is in a metal cabinet): a 1.8 dBi outdoor antenna (104-1041) or a 3.5 dBi outdoor antenna (104-1040), with an RP-SMA to N bulkhead cable of 1 m (102-2012) or 150 mm (102-2011), and optionally an N-male to N-female 90° adapter (800-9207). Option 2, external antenna with a long cable: the Option 1 components plus a super low loss extension cable of 1 m (800-9101), 3 m (800-9102) or 5 m (800-9103) and an N-female to N-female adapter (800-9202). Option 3, puck antenna: the 5 dBi IP65 puck antenna (104-1033), which connects directly through its integrated cable. Option 4, extra long range: the 6 dBi directional antenna (104-1004) with a super low loss cable (1 m, 3 m or 5 m) and a bulkhead cable (1 m or 150 mm); it is highly directional and must be aligned accurately. Before you choose, also look at the radiation pattern of each antenna in Radio planning > Radiation pattern (section ID: radiation-pattern) and pick the one that suits your application.
Manual section: DIN Rail Accessories > Antenna Selector; Radio planning > Radiation pattern > DIN rail > Antennas (section ID: antenna-selector)
See also: Radiation pattern (section ID: radiation-pattern), Wireless best practices (section ID: installation-and-placement-of-wireless-devices-and-external-antennas)
W-Modbus Solar Kit (840-2102): What range can I expect with each antenna?
Also asked as:
- How far apart can the devices be?
- What is the wireless range?
- What distance can I get with an external antenna?
Outdoor line-of-sight estimates: DIN rail in a metal enclosure ~15 m (50 ft); DIN outdoor kit (800-2324) or 1.8 dBi antenna kit (800-2325) ~450 m (1500 ft); 3.5 dBi antenna (104-1040) ~500 m (1650 ft); 5 dBi puck antenna (104-1033) ~100 m (350 ft); 6 dBi directional antenna (104-1004) ~600 m (2000 ft). Real range drops with walls, metal and obstructions. Also look at the radiation pattern of each antenna in Radio planning > Radiation pattern (section ID: radiation-pattern) to choose one that suits your application.
Manual section: Radio planning > Antenna Range estimates; Radio planning > Radiation pattern > DIN rail > Antennas (section ID: antenna-range-estimates)
See also: Radiation pattern (section ID: radiation-pattern), Wireless best practices (section ID: installation-and-placement-of-wireless-devices-and-external-antennas)
W-Modbus Solar Kit (840-2102): How do I swap or fit an external antenna?
Also asked as:
- How do I change the antenna?
- How do I connect an external antenna?
- Can I replace the antenna myself?
Unscrew the stock antenna counter-clockwise, attach the antenna cable connector to the port and twist clockwise until secure, then verify signal strength and adjust placement. For an antenna outside a cabinet, use an RP-SMA to N bulkhead cable of 1 m (102-2012) or 150 mm (102-2011), and orient the antenna according to the radiation pattern in Radio planning > Radiation pattern (section ID: radiation-pattern).
Manual section: Setup Guide > Swap antenna; Radio planning > Radiation pattern > DIN rail > Antennas (section ID: antennas)
See also: Radiation pattern (section ID: radiation-pattern), Wireless best practices (section ID: installation-and-placement-of-wireless-devices-and-external-antennas)
LEDs
W-Modbus Solar Kit (840-2102): What do the LED patterns mean?
Also asked as:
- What do the LED colors mean?
- How do I read the status LEDs?
- What does a blinking blue, green or yellow LED mean?
Read the LEDs top to bottom. Blue sweep = node in commissioning mode; green sweep = gateway in commissioning mode; all blink green = network found; all blink yellow = restarting; all solid red = firmware error (contact support); all blink white = identify. Gateway in secure mode: first LED solid magenta, and the third (RS485) LED blinks green for valid RS485 traffic, red for invalid traffic, and is off when there is no traffic. Node connected: first LED green/yellow/red shows signal strength, and the middle LED blinks green when receiving and blue when transmitting. Node connecting: first LED blinks yellow.
Manual section: LED Status Indicators > LED Pattern Descriptions (section ID: led-pattern-descriptions)
W-Modbus Solar Kit (840-2102): What does the third (RS485) LED tell me?
Also asked as:
- What does the RS485 status LED show?
- Why is the third LED green or red?
- How can I tell if a device is detected on the bus?
On a node, it blinks green (1 s on, 4 s off) when a Modbus RTU device is found and red when none is found. A faster red blink (0.5 s on/off) means the node is scanning for Modbus RTU devices. On the gateway, it blinks green when valid RS485 traffic is received, red when invalid traffic is received, and stays off when there is no bus traffic.
Manual section: LED Status Indicators > LED Pattern Descriptions (section ID: led-pattern-descriptions)
W-Modbus Solar Kit (840-2102): Why did the LEDs turn off?
Also asked as:
- Why are the LEDs no longer on?
- How do I keep the LEDs on permanently?
- Do the LEDs switch off automatically?
LEDs switch off after 30 minutes by default. A single press extends them by 30 minutes; holding the button 5 s (release on magenta) sets them to always on. Since FW 4.2.1 LEDs stay on if an issue is being indicated.
Manual section: LED Status Indicators; Button Functionality (section ID: led-status-indicators)
Button
W-Modbus Solar Kit (840-2102): What does each button press do?
Also asked as:
- What are the button functions?
- What happens if I press the button twice or three times?
- What does holding the button down do?
Single press: keeps the LEDs on for 30 more minutes. Double press: rescans for Modbus RTU devices (the third LED blinks faster while scanning). Triple press: Bluetooth/app mode for 3 minutes (middle LED flashes blue twice). Hold and release on color: 5 s magenta = LEDs always on; 10 s blue = uncommission; 15 s cyan = show firmware version; 20 s red = firmware update (bootloader) mode.
Manual section: Button Functionality (section ID: button-functionality)
W-Modbus Solar Kit (840-2102): How do I factory-reset / uncommission a node?
Also asked as:
- How do I reset a node?
- How do I remove a node from a network?
- How do I put a device back into commissioning mode?
Hold the button for 10 seconds and release when the middle LED shows blue. The device returns to commissioning mode (blue sweep) ready to join a new network. Nodes can also be removed via the app's commissioning screen.
Manual section: Button Functionality > Held button behavior; Mobile App > Removing Commissioned Devices (section ID: held-button-behavior)
DIP switches
W-Modbus Solar Kit (840-2102): How do I set the baud rate with DIP switches?
Also asked as:
- How do I change the baud rate?
- What does each DIP switch do?
- What are the DIP switch settings?
DIP 1/2 set the baud rate: OFF/OFF = 9600, OFF/ON = 19200, ON/OFF = 38400, ON/ON = 76800. DIP 3 sets parity: OFF = none, ON = even. DIP 4 sets stop bits: OFF = 1, ON = 2. DIP 5 (nodes only): ON = use local serial configuration, OFF = use gateway configuration. The default is 9600 baud, no parity, 1 stop bit.
Manual section: Dip Switches; Setup Guide > Set the baud rate on the Gateway (section ID: dip-switches)
W-Modbus Solar Kit (840-2102): What does the three-pole switch do?
Also asked as:
- How do I set the device to gateway or node mode?
- What are the positions of the mode switch?
- How do I switch the gateway to secure mode?
It sets the device role: Gateway = secure gateway, COMM. = gateway commissioning, NODE = mesh node.
Manual section: Dip Switches > Three-Pole-Switch (section ID: three-pole-switch)
Mobile app
W-Modbus Solar Kit (840-2102): What can the W-Modbus mobile app do and what do I need?
Also asked as:
- What can I do with the W-Modbus app?
- What are the requirements for the mobile app?
- How do I connect to a device with the app?
Update firmware, diagnose the network (network map, PDR, range test, diagnostics), show device information, commission nodes, set Modbus addresses, enable Solar mode and replace gateways. You need Bluetooth on, the device powered and within range, and internet access to download firmware. Triple-press the device button to make it connectable for 3 minutes. Use the W-Modbus app: it is separate from the W-BACnet app. While the app is connected, the device has 33% less bandwidth for network traffic.
Manual section: Mobile App > Features / Requirements / Device Connection (section ID: mobile-app)
W-Modbus Solar Kit (840-2102): How do I read the network map?
Also asked as:
- What does the network map show?
- How do I see which nodes are connected?
- What do the colors in the network map mean?
It shows a tree of the gateway and its nodes (children indented under parents). The hexagon to the left of each name shows PDR: green ≥ 99%, amber 94–99%, red < 94%. The RS485 hexagon is green if a local device is connected (red if not), and the Modbus addresses of the connected devices are shown bottom-left. The gateway has no RS485 hexagon, because it acts as the Modbus RTU client. Use Identify (LEDs blink white) and Rename (ASCII, max 8 characters).
Manual section: Mobile App > Network Map (section ID: network-map-overview)
W-Modbus Solar Kit (840-2102): Why are some PDR values missing in the network map?
Also asked as:
- Why does a node show no PDR?
- Why is the PDR blank in the network map?
- Why does a node show limited information in the map?
Nodes may not yet have calculated and sent a PDR to the gateway, or they run firmware older than 3.0.0, which only shows limited information.
Manual section: Mobile App > Network Map > Missing PDR values (section ID: missing-pdr-values)
W-Modbus Solar Kit (840-2102): How do I generate a network map PDF report and why should I?
Also asked as:
- How do I export the network map?
- How do I create an installation report?
- Why do I need to save the network map PDF?
Connect to the gateway, open the network map, select Generate PDF report, optionally add company and installer names, then save or share. Always keep it: it contains the recovery information required to replace a gateway, and support asks for it.
Manual section: Mobile App > PDF Report Generation; Gateway Replacement (section ID: pdf-report-generation)
W-Modbus Solar Kit (840-2102): How do I run a range test?
Also asked as:
- How do I test signal strength between two devices?
- What is range test mode?
- How do I check the wireless link before installing?
Requires FW 4.2.1+ and a commissioned network. In the app, connect to the gateway > Settings > Range Test > toggle on, then do the same on the node. LED 1 shows PDR and LED 3 latency (green good, yellow fair, red weak). Modbus RTU traffic is blocked during the test; disable it on both node and gateway afterwards (auto-exits after 30 min from FW 4.3.0).
Manual section: Mobile App > Range Test Mode; Release Notes 4.3.0 (section ID: range-test-mode)
W-Modbus Solar Kit (840-2102): How do I get diagnostics from a device for support?
Also asked as:
- How do I retrieve device diagnostics in the app?
- What information should I collect for support?
- Where are the diagnostics in the app?
Connect to the device in the app, tap the Settings icon, choose Diagnostics, then tap Get Diagnostics.
Manual section: Mobile App > Device Diagnostics (section ID: how-to-retrieve-diagnostics)
W-Modbus Solar Kit (840-2102): How do I set Modbus addresses manually?
Also asked as:
- Can I assign Modbus addresses myself?
- How do I change a device's Modbus address in the app?
- How do I go back to automatic address assignment?
Modbus addresses are found automatically: each node scans for its connected Modbus RTU devices. To set them manually, connect to the node with the W-Modbus app, tap Set Address Info, enter the address and tap Update Address. The DIN rail supports 1 local device, so enter a single address. To return to automatic address assignment, clear all specified addresses.
Manual section: Mobile App > Setting Modbus Addresses (section ID: setting-modbus-addresses)
W-Modbus Solar Kit (840-2102): How do I install beta firmware?
Also asked as:
- How do I switch to the beta update channel?
- How do I get beta firmware?
- How do I enable beta mode in the app?
When the app starts, tap the LumenRadio logo 8 times and select Beta mode. "Beta Mode" appears in red in the top-right corner.
Manual section: Mobile App > Switching Update Channel (section ID: switching-update-channel)
W-Modbus Solar Kit (840-2102): The app firmware update failed. What should I do?
Also asked as:
- Why did my firmware update fail?
- The app update is stuck – what now?
- What should I do if the update shows an error?
Make sure the device is in range and connected; if it still fails, restart both the app and the W-Modbus device and try again. The W-Modbus app is always the preferred update method. If the update still fails after multiple attempts with the W-Modbus app, use the nRF Connect update flow as a fallback (this flow is also required for devices running firmware below 3.0.0).
Manual section: Mobile App > Mobile App Troubleshooting (section ID: mobile-app-troubleshooting)
Gateway replacement
W-Modbus Solar Kit (840-2102): How do I replace a broken gateway without recommissioning?
Also asked as:
- How do I replace a faulty gateway?
- My gateway is broken – do I have to recommission all nodes?
- What is gateway replacement?
Use Gateway Replacement in the app (Settings > Gateway Replacement). You must have the recovery info from a previously saved Network Map PDF (import the PDF, scan its QR code, or type the 32 recovery numbers). Power off the old gateway permanently, power on the new one, triple-press it, select and identify it in the app to complete. Without saved recovery info, recovery isn't possible.
Manual section: Mobile App > Gateway Replacement (section ID: gateway-replacement)
Radio planning
W-Modbus Solar Kit (840-2102): Where should I place devices and antennas for best signal?
Also asked as:
- How high should I mount the device?
- What are the best practices for antenna placement?
- How do I get the best wireless signal?
Keep ~3/4 inch clearance around the antenna, mount at least 1.5 m (5 ft) above the floor, avoid metal enclosures and surrounding metal, avoid tight antenna-cable bends, and keep outdoor antennas clear of snow. Avoid bottleneck nodes and add repeaters for long or obstructed paths; bring a spare unit to use as a repeater. For the best performance, place and orient the antenna outside any metal cabinet according to the radiation pattern shown in the images in Radio planning > Radiation pattern (section ID: radiation-pattern).
See also: Radiation pattern (section ID: radiation-pattern)
W-Modbus Solar Kit (840-2102): Can I install the Solar Kit units inside a metal electrical cabinet?
Also asked as:
- Will the Solar Kit work inside a metal enclosure?
- Can I mount the units in a steel cabinet?
- What should I do if the units have to go in a metal cabinet?
Yes, but the antenna must sit outside the cabinet with clear line of sight to the other unit's antenna, using the included RP-SMA to N-type cable. Using an antenna inside a metal cabinet drastically reduces range (about 15 m). For the best performance, place and orient the antenna outside the cabinet according to the radiation pattern shown in the images in Radio planning > Radiation pattern (section ID: radiation-pattern).
See also: Radiation pattern (section ID: radiation-pattern), Wireless best practices (section ID: installation-and-placement-of-wireless-devices-and-external-antennas)
W-Modbus Solar Kit (840-2102): How should I position the units to get the best wireless performance?
Also asked as:
- Does the mounting direction of the unit matter?
- How do I use the radiation pattern when installing the units?
- Where is the best place to mount the unit?
- How should I orient the antenna?
Physically install the units according to the radiation pattern shown in the images in Radio planning > Radiation pattern (section ID: radiation-pattern); this gives the best wireless performance. The DIN rail can be installed inside a metal cabinet, but the antenna must then be placed outside the cabinet and oriented according to the radiation pattern of the antenna you use. Using the stock antenna inside a metal cabinet drastically reduces range.
Manual section: Radio planning > Radiation pattern (section ID: radiation-pattern)
See also: Electrical Cabinets (section ID: electrical-cabinets), Antenna Selector (section ID: antenna-selector)
Setup
W-Modbus Solar Kit (840-2102): How do I plan where to place the two units?
Also asked as:
- Where should the GATEWAY and NODE go?
- Do the antennas need line of sight?
- What if there's no line of sight between the inverter and smart meter?
Place the GATEWAY at the inverter and the NODE at the smart meter. Make sure there is clear line of sight between the two antennas – this replaces the cable run. If line of sight is obstructed, add a repeater.
See also: Radiation pattern (section ID: radiation-pattern), Wireless best practices (section ID: installation-and-placement-of-wireless-devices-and-external-antennas)
W-Modbus Solar Kit (840-2102): How do I install the GATEWAY and NODE?
Also asked as:
- How do I connect the kit to my inverter and smart meter?
- What are the installation steps for the Solar Kit?
- How do I wire the Solar Kit units?
GATEWAY: mount it next to the inverter, connect the 24 VDC supply and the RS485 cable (+ and −) to the inverter, keep the antenna outside any metal cabinet with line of sight to the node antenna, then power on. NODE: mount it next to the smart meter, check the switch is set to NODE, connect the 24 VDC supply and RS485 (+ and −) to the smart meter, then power on.
See also: Radiation pattern (section ID: radiation-pattern), Wireless best practices (section ID: installation-and-placement-of-wireless-devices-and-external-antennas)
W-Modbus Solar Kit (840-2102): Do I need to commission the Solar Kit?
Also asked as:
- Is the Solar Kit pre-paired?
- Do I have to pair the gateway and node myself?
- Is the kit plug-and-play?
No. The units are pre-paired and pre-configured, labelled GATEWAY and NODE, so no commissioning is needed out of the box. Commissioning is only needed if you add a repeater. There are two valid ways to do it: the mobile app commissioning method (preferred, and the one used in the Setup Guide) or the physical commissioning method. With the physical method, putting the gateway into commissioning mode also uncommissions the existing node, so it has to rejoin together with the repeater.
Manual section: Setup Guide; Commissioning procedure selector (section ID: setup-guide)
W-Modbus Solar Kit (840-2102): How do I add a repeater?
Also asked as:
- When do I need a repeater?
- How do I commission a repeater to the Solar Kit gateway?
- The link is weak – how do I extend it?
Only needed if no connection is made within 5 minutes or the node's PDR hexagon is red – check the antenna mounting first. The repeater can be commissioned with either of the two valid methods – the mobile app (preferred) or the physical commissioning method. Mobile app method: press the GATEWAY button 3 times; tap Commission in the app, select your gateway (optionally rename it); power on the repeater (LEDs sweep blue) and tap Add. Confirm in the network map that the repeater has joined and the smart-meter node now shows yellow or green PDR. A repeater's right LED is solid red because it has no local device.
See also: Radiation pattern (section ID: radiation-pattern), Wireless best practices (section ID: installation-and-placement-of-wireless-devices-and-external-antennas)
W-Modbus Solar Kit (840-2102): What should the LEDs show after installation?
Also asked as:
- How do I know the Solar Kit is working from the LEDs?
- What LED colors should the GATEWAY and NODE show?
- What do the LEDs look like when the link is up?
GATEWAY: solid magenta left LED, blinking green right LED, fast blinking blue/green middle LED. NODE: solid green left LED, blinking green right LED, fast blinking blue/green middle LED.
Manual section: Setup Guide > 5. Check the LED indicators (section ID: 5-check-the-led-indicators)
W-Modbus Solar Kit (840-2102): How do I verify my installation is working?
Also asked as:
- How do I check the Solar Kit installation works?
- What should the app show after installation?
- How do I check the link quality?
Press the GATEWAY button 3 times and connect with the W-Modbus app. In the device view, confirm Solar Mode is on and the app shows 1 wireless device and 1 Modbus device. Then open the Network map: the node's PDR hexagon should be green or yellow; if it is red, add a repeater.
See also: Radiation pattern (section ID: radiation-pattern), Wireless best practices (section ID: installation-and-placement-of-wireless-devices-and-external-antennas)
Application
W-Modbus Solar Kit (840-2102): What RS485 settings should the inverter and smart meter use?
Also asked as:
- What are the default serial settings of the Solar Kit?
- What baud rate does the Solar Kit use?
- Do the inverter and smart meter need matching settings?
Both units ship with 9600 baud, no parity and 1 stop bit. Configure the inverter and smart meter with the same settings.
Manual section: Application Guide > RS485 defaults; Setup Guide > 4. Verify RS485 settings (section ID: rs485-defaults)
W-Modbus Solar Kit (840-2102): Can I monitor the wireless network from my Modbus client (remote diagnostics)?
Also asked as:
- Can I read network diagnostics over Modbus?
- Which registers show the wireless network status?
- What address does the gateway use for diagnostics?
The gateway also acts as a Modbus RTU server and exposes wireless network diagnostics in holding registers, read with function code 3 (Read Holding Registers) at the default address 201. Remote diagnostics over Modbus is available only from gateway firmware 4.3.0; earlier firmware does not expose these registers, so update the gateway first. The registers must be configured manually in your Modbus client. Key registers: 30 = number of wireless nodes; 31 = number of Modbus server devices; 32–34 = firmware major/minor/patch; 35–36 = nodes that received/installed the latest firmware; 37 = Solar mode enabled; 57 = RSSI to parent; 59–60 = uptime in hours; 101–200 = PDR per node (255 = no valid link); 301–400 = parent node ID (255 = direct link to the gateway); 501–600 = RS485 bus configuration per node; 801–1800 = node names; 2000–3599 = Modbus addresses per node. Register availability depends on the gateway firmware version. On site, connect to the gateway with the W-Modbus mobile app and open the network map: the hexagon next to each node shows its PDR (packet delivery ratio), see Mobile App > Network Map > PDR (section ID: pdr).
Manual section: Remote Diagnostics > Register mapping; Release Notes > 4.3.0 (section ID: remote-diagnostics)
W-Modbus Solar Kit (840-2102): Is Solar mode enabled on the Solar Kit?
Also asked as:
- Do I need to turn on Solar mode?
- How do I check Solar mode is on?
- What does Solar mode do?
Yes, it ships pre-enabled. Solar mode handles inverters that expect a reply within 100 ms or less. To check, connect to the GATEWAY with the W-Modbus app and confirm the Solar Mode switch on the home screen is on. It needs firmware 4.2.0 or later and the latest app. Toggling it restarts the gateway and the node rejoins, causing a brief downtime.
Manual section: Application Guide > Solar Mode (section ID: solar-mode)
W-Modbus Solar Kit (840-2102): Which inverters and smart meters are compatible with the Solar Kit?
Also asked as:
- Has my inverter been tested with the Solar Kit?
- Is there a compatibility list?
- What if my inverter isn't on the list?
Tested pairs include Fronius Symo GEN24, Growatt MOD series, Huawei SUN2000, Kostal PLENTICORE, SAJ H2, Sigenergy SigenStor, Solinteg, Solis S6 and Sungrow, mostly with CHINT DTSU666 or Eastron SDM630 meters. SolaX X3-Hybrid G4.2 and Fox ESS H3 are not yet tested. LumenRadio can't guarantee compatibility, so disable automatic firmware updates on the inverter and meter if possible. If your pair isn't listed or stops working, raise a support ticket.
Remote diagnostics
W-Modbus Solar Kit (840-2102): How do I monitor the wireless performance of my W-Modbus network?
Also asked as:
- How do I check the health of the wireless network?
- How can I see the signal quality of each node?
- How do I know if the wireless links are good enough?
There are two ways:
- In the mobile app: connect to the gateway with the W-Modbus mobile app and open the network map. The hexagon next to each node shows its PDR (packet delivery ratio): green ≥ 99%, amber 94–99%, red < 94%. Aim for a PDR above 95% on every node. See Mobile App > Network Map > PDR (section ID: pdr).
- Remotely in your BMS, Niagara, SCADA or other Modbus client: the gateway exposes the wireless network metrics, including per-node PDR, RSSI and link quality, through remote diagnostics. Requires gateway firmware 4.3.0 or later. See Remote Diagnostics (section ID: remote-diagnostics).
Manual section: Mobile App > Network Map > PDR (section ID: pdr); Remote Diagnostics (section ID: remote-diagnostics)
W-Modbus Solar Kit (840-2102): Can I see the wireless diagnostics in Niagara or another BMS?
Also asked as:
- How do I show the wireless network diagnostics in Niagara?
- Are the wireless diagnostics visible remotely in my BMS or SCADA system?
- Can my BMS read the network health, PDR and signal strength of the nodes?
Yes. Any BMS or controller that works as a Modbus RTU client (master), such as Niagara, can read them. The gateway answers on Modbus address 201 and exposes the wireless network metrics as holding registers (function code 0x03). Remote diagnostics over Modbus is available only from gateway firmware 4.3.0; earlier firmware does not expose these registers, so update the gateway first. Add the registers you need to your Modbus client using the register map in the manual. On site, connect to the gateway with the W-Modbus mobile app and open the network map: the hexagon next to each node shows its PDR (packet delivery ratio), see Mobile App > Network Map > PDR (section ID: pdr).
Manual section: Remote Diagnostics (section ID: remote-diagnostics)
Troubleshooting
W-Modbus Solar Kit (840-2102): The RS485 LED is red / no RS-485 device detected. What do I do?
Also asked as:
- Why is my RS485 device not detected?
- The third LED is red – what does it mean?
- Why can't the node find the connected device?
Check RS485 polarity and the bus settings (baud rate, parity, stop bits). Make sure the Modbus RTU client (master) is connected to the W-Modbus Gateway and the servers (slaves) are connected to the nodes. In solar installations, the inverter must be connected at the Gateway and the smart meter at the Node, with the gateway in Solar mode. Confirm the Modbus RTU device itself works.
Manual section: Troubleshooting > No RS-485 device detected (section ID: no-rs-485-device-detected)
W-Modbus Solar Kit (840-2102): Nodes aren't connecting to the gateway. What should I check?
Also asked as:
- Why won't my node join the gateway?
- A node is missing from the network – what should I check?
- Why is my node blinking yellow?
Check which of the two commissioning methods you are using – both are valid, and the mobile app method is preferred. Mobile app method: confirm the gateway is in secure mode and that you tapped Add for each node in the app. Physical method: confirm the gateway is in commissioning mode and the nodes are in commissioning mode (blue sweep). In both cases, check that nothing is still in range test mode, and that nodes are within range; move closer or add repeaters/external antennas.
Manual section: Troubleshooting > Wireless > Nodes are not connecting (section ID: nodes-are-not-connecting-to-gateway)
W-Modbus Solar Kit (840-2102): Some nodes stay in secure mode after I switched the gateway back to commissioning. Why?
Also asked as:
- Why didn't all nodes return to commissioning mode?
- Some nodes didn't follow the gateway into commissioning mode – what now?
- How do I get all nodes back into commissioning mode?
Those nodes hadn't rejoined the gateway in time to get the instruction. Put the gateway back in secure mode for 10 minutes so all nodes rejoin, then switch to commissioning; or uncommission each node manually (hold button 10 s).
Manual section: Troubleshooting > Wireless (section ID: when-i-put-the-gateway-back-into-commissioning-mode-some-nodes-stay-in-secure-mode)
W-Modbus Solar Kit (840-2102): Where should the GATEWAY and NODE be connected in a solar installation?
Also asked as:
- Which unit goes on the inverter?
- Should the smart meter be on the gateway or the node?
- I swapped the units – does it matter?
The GATEWAY must always be at the inverter (it polls as the Modbus client) and the NODE at the smart meter. Repeater nodes can sit between them if needed.
Firmware
W-Modbus Solar Kit (840-2102): What is the latest firmware and how do I check my version?
Also asked as:
- Which firmware version is the latest?
- How do I check which firmware a device runs?
- How do I read the firmware version from the LEDs?
Latest is 4.3.1 (released 2026-11-18). Check in the app, or hold the button 15 s and release on cyan: the top LED blinks the major number, the middle LED the minor and the bottom LED the patch (e.g., 3-3-2 blinks = 3.3.2).
Manual section: Firmware Updates > Checking Current Version (section ID: checking-current-version)
W-Modbus Solar Kit (840-2102): How do I update firmware without the W-Modbus app?
Also asked as:
- How do I update firmware with nRF Connect?
- Can I update firmware without the W-Modbus app?
- How do I update devices with very old firmware?
The preferred way to update firmware is always through the W-Modbus app. Use the nRF Connect update flow only if the device runs firmware below 3.0.0, or as a fallback after multiple failed update attempts with the W-Modbus app: download the firmware zip from LumenRadio, install nRF Connect, hold the button for 20 s until the middle LED turns red (bootloader mode), scan and connect to the W-Modbus-DFU device, select the file via the DFU icon and wait for "Application has been sent successfully". Below 3.0.0, FOTA is not available, so every device must be updated this way. From 3.0.0 onwards, update only the gateway and FOTA updates the nodes.
Manual section: Firmware Updates > Update Procedures > nRF Connect (section ID: nrf-connect)
W-Modbus Solar Kit (840-2102): What changed in firmware 4.3.0 and are there known issues?
Also asked as:
- What's new in firmware 4.3.0?
- What are the known issues in the latest firmware?
- Where can I find the release notes?
Released 2026-09-07. Added: improved Solar mode compatibility, wireless network diagnostics readable over Modbus RTU, and support for the OEM Module Development Kit MK2. Changed: range test mode exits automatically after 30 minutes. Fixed: failures when fetching network information via the app, and intermittent RS485 communication failures. Known issues: bandwidth is reduced by 33% while the app is connected; downgrading below 3.0.0 factory-resets the device.
Manual section: Firmware Updates > Release Notes > 4.3.0 (section ID: 430)
Support
W-Modbus Solar Kit (840-2102): How long is the warranty and what voids it?
Also asked as:
- What is the warranty period?
- What voids the warranty?
- Is the device covered by warranty?
Warranty length is set by your distributor, typically 1–5 years from shipment. It is void if the product is repaired or modified without LumenRadio approval, or the serial number is missing or illegible. Defects must be reported in writing within 15 days of discovery.
Manual section: Warranty and Support > Warranty Terms / Return and complaint policy (section ID: warranty-terms)
W-Modbus Solar Kit (840-2102): Who should I contact for support and what should I include?
Also asked as:
- How do I contact support?
- What information should I include in a support ticket?
- How do I raise a support ticket?
Contact your installer or distributor first for installation, wiring, power, configuration and warranty questions; contact LumenRadio support for firmware errors (e.g., all LEDs solid red) or unresolved issues via Create Support Ticket. Include symptoms, product/serial/firmware, controller make and model, steps tried, photos, LED video, network map PDF/PDR, power type, bus settings, wireless conditions and antennas used.
Manual section: Warranty and Support > When to Contact Support / What to include (section ID: when-to-contact-support)
W-Modbus Solar Kit (840-2102): How do I file an RMA?
Also asked as:
- How do I return a faulty device?
- How do I make a warranty claim?
- What does an RMA request need to include?
Submit an RMA claim through the LumenRadio support system with the product serial numbers, a clear fault description, and details of how the device was installed.
Manual section: Warranty and Support > RMA claims (section ID: rma-claims)
Regulatory
W-Modbus Solar Kit (840-2102): What certifications does the product have?
Also asked as:
- Is the product CE or FCC certified?
- Which regulatory approvals does it have?
- Which countries is the product certified for?
CE (RED 2014/53/EU), UKCA, FCC Part 15 Class B (FCC IDs XRSTIMOMWAN301, XRSTIMOMWAN201), Industry Canada/ISED, MIC (Japan) and KC (South Korea), with 2.4 GHz approvals listed for China, India, Australia, South Africa, Malaysia and Vietnam. Keep at least 20 cm between antenna and people (FCC exposure).
Manual section: Regulatory Compliance (section ID: regulatory-compliance)
W-Modbus Solar Kit (840-2102): Is the W-Modbus wireless communication encrypted and secure?
Also asked as:
- What encryption does W-Modbus use?
- How is W-Modbus protected against hacking?
- What security features does W-Modbus have?
Yes. All data sent over the W-Modbus wireless mesh is encrypted with AES-128, and only devices with the network credentials can join the mesh. Configuration requires physical access to the device, network keys are only shared as encrypted blobs that only W-Modbus devices can decrypt, and firmware updates are signed and verified on every device.
Manual section: Security features (section ID: security-features)
W-Modbus Solar Kit (840-2102): Can W-Modbus be accessed or managed from the internet?
Also asked as:
- Does W-Modbus have an IP or cloud connection?
- Can someone reach the W-Modbus devices remotely over the network?
- Does W-Modbus support remote management?
No. W-Modbus devices have no Ethernet, Wi-Fi or other interface to an external IP network, no border-router function and no cloud or remote management interface. IPv6 is used only for internal addressing inside the encrypted MiraMesh network. The devices cannot be configured, managed or updated from the internet or over the Modbus interface.
Manual section: Interfaces (section ID: interfaces)
W-Modbus Solar Kit (840-2102): Can someone change the W-Modbus configuration over Bluetooth without physical access?
Also asked as:
- Is Bluetooth always on?
- How is configuration over BLE protected?
- How close do I need to be to connect with the mobile app?
No. W-Modbus devices do not advertise over Bluetooth Low Energy (BLE) by default. Press the button on the device three times to make it connectable; it then advertises for 3 minutes and stops if no connection is made. A connected session disconnects automatically after 2 minutes of inactivity. The BLE connection uses only the on-chip antenna, so you normally need to be within 2–3 m of the device.
Manual section: Configuration requires physical access (section ID: configuration-requires-physical-access)
W-Modbus Solar Kit (840-2102): How are W-Modbus firmware updates protected?
Also asked as:
- Are firmware updates signed?
- Can someone install malicious firmware on W-Modbus?
- How do I know a firmware update is genuine?
Every firmware file is digitally signed. The update is sent from the mobile app over BLE to the gateway, which distributes it to the nodes as AES-128-encrypted mesh messages. The gateway and each node check the signature before installing; if the check fails, that device rejects the update and keeps its current firmware. Updates can only start over BLE, so they need physical access to the gateway.
Manual section: Secure firmware updates (section ID: secure-firmware-updates)
W-Modbus Solar Kit (840-2102): Does W-Modbus comply with the RED cybersecurity requirements (EN 18031)?
Also asked as:
- Is W-Modbus in scope of RED Article 3(3)(d), (e) or (f)?
- Does W-Modbus need EN 18031-1 certification?
- What about Delegated Regulation (EU) 2022/30?
LumenRadio has assessed W-Modbus as outside the scope of RED Article 3(3)(d), because it has no interface to any external IP network and cannot communicate over the internet, so no Notified Body evaluation against EN 18031-1 is required. Article 3(3)(e) does not apply because W-Modbus does not process personal data, and Article 3(3)(f) does not apply because it has no financial functions. W-Modbus still includes security measures in line with the intent of EN 18031-1.
Manual section: EU Radio Equipment Directive – Article 3(3)(d), (e), (f) (section ID: eu-radio-equipment-directive-article-33d-e-f)
W-Modbus Solar Kit (840-2102): What is the system integrator responsible for to keep a W-Modbus installation secure?
Also asked as:
- How do I secure my W-Modbus installation?
- What security best practices should I follow?
- Who is responsible for network security on the IP side?
Secure the Modbus master (BMS, SCADA system or controller) with access control, strong passwords and up-to-date software; install the devices where unauthorized people can't easily reach them, such as locked cabinets or plant rooms; keep the firmware up to date through the mobile app; and treat Modbus as unauthenticated by restricting who and what can reach the Modbus master.
Manual section: Responsibilities of the system integrator (section ID: responsibilities-of-the-system-integrator)
W-Modbus Solar Kit (840-2102): How do I report a security vulnerability in W-Modbus?
Also asked as:
- Where can I report a security issue?
- Who do I contact about a cybersecurity problem?
- Does LumenRadio have a vulnerability disclosure process?
Submit a request through the LumenRadio support portal. Include the product name, firmware version and a description of the issue, and do not disclose the vulnerability publicly until LumenRadio has had the chance to investigate and respond.
Manual section: Reporting security issues (section ID: reporting-security-issues)