W-Modbus Wall mount PRO (840-2114) customer Q&A

Every answer on this page applies only to the W-Modbus Wall mount PRO (SKU 840-2114, Modbus RTU). Do not use these answers for other LumenRadio products or form factors. Full manual: W-Modbus Wall mount PRO manual

Product overview

W-Modbus Wall mount PRO (840-2114): What is W-Modbus Wall mount PRO and what does it do?

Also asked as:

W-Modbus replaces the RS485 control cable in a Modbus RTU installation with a wireless mesh link, removing the need for daisy-chaining, cable planning and cable troubleshooting while keeping standard Modbus RTU compatibility. A unit can act as the Gateway (connected to the Modbus RTU client) or as a mesh Node (connected to one or more Modbus RTU servers). W-Modbus is built on LumenRadio's MiraOS, which runs the MiraMesh network stack.

Manual section: Introduction > Product Overview (section ID: product-overview)

W-Modbus Wall mount PRO (840-2114): How many devices can a W-Modbus network support?

Also asked as:

A W-Modbus network supports up to 100 mesh nodes per gateway, although the recommended size may be lower depending on the radio environment and network topology. Each Wall mount PRO node supports up to 4 local Modbus RTU server devices. The Modbus RTU client is always connected at the gateway. If you have more than 25 Modbus RTU devices that require a fast response rate, split the system into two or more networks.

Manual section: Introduction > Product Overview; Radio planning > Wireless design considerations; Device Overview > Specifications (section ID: product-overview)

W-Modbus Wall mount PRO (840-2114): What is the difference between Wall mount and Wall mount PRO?

Also asked as:

They are identical except that the PRO supports up to 4 connected local Modbus RTU devices when used as a mesh node, versus 1 on the standard Wall mount. Both can be used as Gateway or Node.

Manual section: Introduction > Glossary of Terms (section ID: glossary-of-terms)

W-Modbus Wall mount PRO (840-2114): What is the difference between a Gateway and a Node?

Also asked as:

The Gateway is the central root device of the network, and all wireless unicast messages pass through it. The Modbus RTU client (master) must be connected to the Gateway to query devices on the nodes. Nodes connect to Modbus RTU servers (slaves), and every node also acts as a repeater automatically, even with no Modbus device connected. Use only one Gateway per network; choose a DIN rail or Wall mount as the Gateway. Any form factor (Compact, DIN rail, DIN rail PRO, Wall mount or Wall mount PRO) can be a node.

Manual section: Glossary of Terms; System Description > W-Modbus Mesh Network; Radio planning > Gateway & Node selection (section ID: gateway-node-selection)

Safety

W-Modbus Wall mount PRO (840-2114): What safety precautions apply when installing the device?

Also asked as:

Disconnect power before wiring, verify the supply matches spec and check DC polarity, use correctly rated wiring and overcurrent protection, follow local electrical codes, use ESD protection, and have only qualified technicians install it. Do not install in wet locations or above 95% RH, do not use if damaged, and do not use for safety-critical tasks.

Manual section: Safety Information; Warnings and Precautions (section ID: safety-information)

W-Modbus Wall mount PRO (840-2114): What should I watch out for when sharing a power supply with other devices?

Also asked as:

W-Modbus uses a half-wave rectified circuit, so it should not share a VAC transformer with a device that uses a full-wave rectified circuit. A shared transformer is only acceptable if the other devices are also half-wave rectified and all power connections have the same polarity: the W-Modbus "+" terminal must never be connected to the "–" terminal of another device. When connecting a 24 V isolation transformer, follow IEC 61558-1.

Manual section: Safety Information > Electrical Safety / Power and RS485 Circuit Caution (section ID: power-and-rs485-circuit-caution)

Specifications

W-Modbus Wall mount PRO (840-2114): What are the power requirements?

Also asked as:

24 VAC ±10% or 24 VDC ±10%. Maximum consumption is 2 W (average 0.6 W), with up to 10 W of 24 V throughput power. Troubleshooting guidance asks for a supply that can deliver at least 0.5 A.

Manual section: Device Overview > Specifications; Troubleshooting > None of the LEDs are blinking (section ID: specifications)

W-Modbus Wall mount PRO (840-2114): What are the physical and environmental specs of the Wall mount PRO unit?

Also asked as:

86 × 86 × 25 mm, 95 g, IP40, internal antenna. Operating temperature −20 °C to +55 °C (−4 °F to 131 °F), storage −30 °C to +80 °C, humidity 10–95% non-condensing. Terminals accept 0.2–0.5 mm² stranded or 0.14–0.5 mm² solid conductors (AWG 24–20).

Manual section: Device Overview > Specifications (section ID: specifications)

W-Modbus Wall mount PRO (840-2114): What radio frequency and output power does it use?

Also asked as:

2402–2480 MHz (2.4 GHz band) with maximum RF output power of 100 mW. Network traffic is encrypted with AES-128 using credentials unique to each gateway.

Manual section: Device Overview > Specifications; System Description > W-Modbus Mesh Network (section ID: specifications)

W-Modbus Wall mount PRO (840-2114): Does the Wall mount PRO have a termination resistor, and can I disable it?

Also asked as:

Yes, it has a built-in 120 Ω end-of-line resistor that cannot be disabled. Place the unit at one end of the RS485 trunk and terminate the other end with a 120 Ω resistor (built-in or external).

Manual section: Setup Guide > Wiring > Wiring Diagram; Troubleshooting > Can the EOL resistor be disabled? (section ID: wiring-diagram)

Device overview

W-Modbus Wall mount PRO (840-2114): What are the physical components on the device?

Also asked as:

From the device overview: LEDs, RS485 bus-settings DIP switch, push button, 3-way mode switch, power connector, RS485 bus connector, knockout for cable entry, and internal LEDs that show the same as the front LEDs. There is no antenna connector.

Manual section: Device Overview (section ID: device-overview)

System

W-Modbus Wall mount PRO (840-2114): What is the difference between commissioning mode and secure mode?

Also asked as:

Commissioning mode uses known, shared credentials so new nodes can find and join a gateway. When the gateway is switched to secure mode, all nodes reboot together and switch to encrypted credentials unique to that gateway for long-term operation, so nearby networks don't interfere.

Manual section: System Description > Commissioning Network / Secure Network (section ID: commissioning-network)

W-Modbus Wall mount PRO (840-2114): How does the gateway share its serial settings with nodes?

Also asked as:

The gateway distributes its bus settings (baud rate, parity and stop bits) to all nodes. Wall mount and DIN rail nodes use the gateway configuration unless DIP switch 5 (use local serial configuration) is ON. Compact nodes always take their settings from the gateway. As long as Wall mounts and DIN rails are used as nodes, different baud rates can be mixed in one system.

Manual section: System Description > Config Distribution; Setup Guide > Set the baud rate on the Gateway (section ID: config-distribution)

W-Modbus Wall mount PRO (840-2114): What is FOTA and do I need to update every node?

Also asked as:

Firmware-Over-The-Air (from FW 3.0.0) lets the gateway push new firmware to every node in a secure network automatically. Update only the gateway, preferably through the W-Modbus app; propagation typically takes 30 minutes to 2 hours depending on network size. Progress is shown via FOTA Status in the app. If the devices run firmware below 3.0.0, FOTA is not available and they must be updated using the nRF Connect update flow.

Manual section: System Description > FOTA; Mobile App > Complete update / FOTA status (section ID: firmware-over-the-air-fota)

Accessories

W-Modbus Wall mount PRO (840-2114): What accessories are available for the Wall mount PRO?

Also asked as:

The accessories in the manual (outdoor kit, IP67 enclosure, external antennas, antenna cables, DIN rail power supply and outer shell) are designed for the DIN rail form factor. Only the DIN rail supports external antennas, so these do not apply to the Wall mount PRO. Check with your distributor for accessories available for the Wall mount PRO.

Manual section: DIN Rail Accessories > Available Accessories (section ID: specifications)

W-Modbus Wall mount PRO (840-2114): How do I install W-Modbus outdoors?

Also asked as:

Place the device in a suitably rated IP enclosure to protect it from dust and moisture, and mount it where snow cannot build up around it. The DIN Outdoor Kit (800-2324) is designed for the DIN rail form factor. The Wall mount PRO must not be installed in a metal enclosure; where a metal enclosure is required, use a DIN rail unit with its antenna mounted outside the enclosure.

Manual section: Radio planning > Outdoor Installations; Radio planning > Radiation pattern > Wall mount (section ID: outdoor-installations)

See also: Radiation pattern (section ID: radiation-pattern), Wireless best practices (section ID: installation-and-placement-of-wireless-devices-and-external-antennas)

W-Modbus Wall mount PRO (840-2114): Can I use a third-party antenna?

Also asked as:

No. Only the DIN rail supports external antennas; the Wall mount PRO uses its built-in antenna. If your installation needs an external or high-gain antenna, use a DIN rail unit.

Manual section: Radio planning > Wireless design considerations (section ID: specifications)

W-Modbus Wall mount PRO (840-2114): Which antenna setup should I choose?

Also asked as:

The antenna options in the manual (external omni antenna, long cable, puck antenna and directional antenna) apply only to the DIN rail. The Wall mount PRO uses its built-in antenna, so focus on placement: mount it at least 1.5 m above the floor, keep it clear of metal and obstructions, and never install it inside a metal cabinet or enclosure. For the best performance, physically install the unit according to the radiation pattern shown in the images in Radio planning > Radiation pattern (section ID: radiation-pattern).

Manual section: Radio planning > Wireless design considerations / Installation Guidelines; Radio planning > Radiation pattern > Wall mount (section ID: specifications)

See also: Radiation pattern (section ID: radiation-pattern), Wireless best practices (section ID: installation-and-placement-of-wireless-devices-and-external-antennas)

W-Modbus Wall mount PRO (840-2114): What range can I expect with each antenna?

Also asked as:

The range estimates in the manual (up to 600 m line of sight) are for the DIN rail and its external antenna accessories. Range for the Wall mount PRO depends on placement and surroundings, and is lower where walls, metal and other obstructions are present. Use the radiation pattern and LumenRadio's wireless range calculator to plan, and run a range test to confirm. Do not install the Wall mount PRO inside a metal cabinet or enclosure, as the metal severely attenuates the signal.

Manual section: Radio planning > Antenna Range estimates; Mobile App > Range Test Mode; Radio planning > Radiation pattern > Wall mount (section ID: antenna-range-estimates)

See also: Radiation pattern (section ID: radiation-pattern), Wireless best practices (section ID: installation-and-placement-of-wireless-devices-and-external-antennas)

W-Modbus Wall mount PRO (840-2114): How do I swap or fit an external antenna?

Also asked as:

This does not apply to the Wall mount PRO: only the DIN rail supports external antennas.

Manual section: Radio planning > Wireless design considerations; Radio planning > Radiation pattern > Wall mount (section ID: specifications)

See also: Radiation pattern (section ID: radiation-pattern), Wireless best practices (section ID: installation-and-placement-of-wireless-devices-and-external-antennas)

LEDs

W-Modbus Wall mount PRO (840-2114): What do the LED patterns mean?

Also asked as:

Read the LEDs top to bottom. Blue sweep = node in commissioning mode; green sweep = gateway in commissioning mode; all blink green = network found; all blink yellow = restarting; all solid red = firmware error (contact support); all blink white = identify. Gateway in secure mode: first LED solid magenta, and the third (RS485) LED blinks green for valid RS485 traffic, red for invalid traffic, and is off when there is no traffic. Node connected: first LED green/yellow/red shows signal strength, and the middle LED blinks green when receiving and blue when transmitting. Node connecting: first LED blinks yellow.

Manual section: LED Status Indicators > LED Pattern Descriptions (section ID: led-pattern-descriptions)

W-Modbus Wall mount PRO (840-2114): What does the third (RS485) LED tell me?

Also asked as:

On a node, it blinks green (1 s on, 4 s off) when a Modbus RTU device is found and red when none is found. A faster red blink (0.5 s on/off) means the node is scanning for Modbus RTU devices. On the gateway, it blinks green when valid RS485 traffic is received, red when invalid traffic is received, and stays off when there is no bus traffic.

Manual section: LED Status Indicators > LED Pattern Descriptions (section ID: led-pattern-descriptions)

W-Modbus Wall mount PRO (840-2114): Why did the LEDs turn off?

Also asked as:

LEDs switch off after 30 minutes by default. A single press extends them by 30 minutes; holding the button 5 s (release on magenta) sets them to always on. Since FW 4.2.1 LEDs stay on if an issue is being indicated.

Manual section: LED Status Indicators; Button Functionality (section ID: led-status-indicators)

Button

W-Modbus Wall mount PRO (840-2114): What does each button press do?

Also asked as:

Single press: keeps the LEDs on for 30 more minutes. Double press: rescans for Modbus RTU devices (the third LED blinks faster while scanning). Triple press: Bluetooth/app mode for 3 minutes (middle LED flashes blue twice). Hold and release on color: 5 s magenta = LEDs always on; 10 s blue = uncommission; 15 s cyan = show firmware version; 20 s red = firmware update (bootloader) mode.

Manual section: Button Functionality (section ID: button-functionality)

W-Modbus Wall mount PRO (840-2114): How do I factory-reset / uncommission a node?

Also asked as:

Hold the button for 10 seconds and release when the middle LED shows blue. The device returns to commissioning mode (blue sweep) ready to join a new network. Nodes can also be removed via the app's commissioning screen.

Manual section: Button Functionality > Held button behavior; Mobile App > Removing Commissioned Devices (section ID: held-button-behavior)

DIP switches

W-Modbus Wall mount PRO (840-2114): How do I set the baud rate with DIP switches?

Also asked as:

DIP 1/2 set the baud rate: OFF/OFF = 9600, OFF/ON = 19200, ON/OFF = 38400, ON/ON = 76800. DIP 3 sets parity: OFF = none, ON = even. DIP 4 sets stop bits: OFF = 1, ON = 2. DIP 5 (nodes only): ON = use local serial configuration, OFF = use gateway configuration. The default is 9600 baud, no parity, 1 stop bit.

Manual section: Dip Switches; Setup Guide > Set the baud rate on the Gateway (section ID: dip-switches)

W-Modbus Wall mount PRO (840-2114): What does the three-pole switch do?

Also asked as:

It sets the device role: ◼ = secure gateway, ◻ = gateway commissioning, ● = mesh node.

Manual section: Dip Switches > Three-Pole-Switch (section ID: three-pole-switch)

Mobile app

W-Modbus Wall mount PRO (840-2114): What can the W-Modbus mobile app do and what do I need?

Also asked as:

Update firmware, diagnose the network (network map, PDR, range test, diagnostics), show device information, commission nodes, set Modbus addresses, enable Solar mode and replace gateways. You need Bluetooth on, the device powered and within range, and internet access to download firmware. Triple-press the device button to make it connectable for 3 minutes. Use the W-Modbus app: it is separate from the W-BACnet app. While the app is connected, the device has 33% less bandwidth for network traffic.

Manual section: Mobile App > Features / Requirements / Device Connection (section ID: mobile-app)

W-Modbus Wall mount PRO (840-2114): How do I read the network map?

Also asked as:

It shows a tree of the gateway and its nodes (children indented under parents). The hexagon to the left of each name shows PDR: green ≥ 99%, amber 94–99%, red < 94%. The RS485 hexagon is green if a local device is connected (red if not), and the Modbus addresses of the connected devices are shown bottom-left. The gateway has no RS485 hexagon, because it acts as the Modbus RTU client. Use Identify (LEDs blink white) and Rename (ASCII, max 8 characters).

Manual section: Mobile App > Network Map (section ID: network-map-overview)

W-Modbus Wall mount PRO (840-2114): Why are some PDR values missing in the network map?

Also asked as:

Nodes may not yet have calculated and sent a PDR to the gateway, or they run firmware older than 3.0.0, which only shows limited information.

Manual section: Mobile App > Network Map > Missing PDR values (section ID: missing-pdr-values)

W-Modbus Wall mount PRO (840-2114): How do I generate a network map PDF report and why should I?

Also asked as:

Connect to the gateway, open the network map, select Generate PDF report, optionally add company and installer names, then save or share. Always keep it: it contains the recovery information required to replace a gateway, and support asks for it.

Manual section: Mobile App > PDF Report Generation; Gateway Replacement (section ID: pdf-report-generation)

W-Modbus Wall mount PRO (840-2114): How do I run a range test?

Also asked as:

Requires FW 4.2.1+ and a commissioned network. In the app, connect to the gateway > Settings > Range Test > toggle on, then do the same on the node. LED 1 shows PDR and LED 3 latency (green good, yellow fair, red weak). Modbus RTU traffic is blocked during the test; disable it on both node and gateway afterwards (auto-exits after 30 min from FW 4.3.0).

Manual section: Mobile App > Range Test Mode; Release Notes 4.3.0 (section ID: range-test-mode)

W-Modbus Wall mount PRO (840-2114): How do I get diagnostics from a device for support?

Also asked as:

Connect to the device in the app, tap the Settings icon, choose Diagnostics, then tap Get Diagnostics.

Manual section: Mobile App > Device Diagnostics (section ID: how-to-retrieve-diagnostics)

W-Modbus Wall mount PRO (840-2114): How do I set Modbus addresses manually?

Also asked as:

Modbus addresses are found automatically: each node scans for its connected Modbus RTU devices. To set them manually, connect to the node with the W-Modbus app, tap Set Address Info, enter the addresses and tap Update Address(es). On PRO units you can enter up to 4 addresses. If you enter fewer addresses than there are connected devices, only the devices with assigned addresses are visible; the rest are not discovered. To return to automatic address assignment, clear all specified addresses.

Manual section: Mobile App > Setting Modbus Addresses (section ID: setting-modbus-addresses)

W-Modbus Wall mount PRO (840-2114): How do I install beta firmware?

Also asked as:

When the app starts, tap the LumenRadio logo 8 times and select Beta mode. "Beta Mode" appears in red in the top-right corner.

Manual section: Mobile App > Switching Update Channel (section ID: switching-update-channel)

W-Modbus Wall mount PRO (840-2114): The app firmware update failed. What should I do?

Also asked as:

Make sure the device is in range and connected; if it still fails, restart both the app and the W-Modbus device and try again. The W-Modbus app is always the preferred update method. If the update still fails after multiple attempts with the W-Modbus app, use the nRF Connect update flow as a fallback (this flow is also required for devices running firmware below 3.0.0).

Manual section: Mobile App > Mobile App Troubleshooting (section ID: mobile-app-troubleshooting)

Gateway replacement

W-Modbus Wall mount PRO (840-2114): How do I replace a broken gateway without recommissioning?

Also asked as:

Use Gateway Replacement in the app (Settings > Gateway Replacement). You must have the recovery info from a previously saved Network Map PDF (import the PDF, scan its QR code, or type the 32 recovery numbers). Power off the old gateway permanently, power on the new one, triple-press it, select and identify it in the app to complete. Without saved recovery info, recovery isn't possible.

Manual section: Mobile App > Gateway Replacement (section ID: gateway-replacement)

Radio planning

W-Modbus Wall mount PRO (840-2114): Where should I place devices and antennas for best signal?

Also asked as:

Keep ~3/4 inch clearance around the antenna, mount at least 1.5 m (5 ft) above the floor, never install the Wall mount PRO inside a metal cabinet or enclosure, keep it clear of surrounding metal, and keep outdoor antennas clear of snow. Avoid bottleneck nodes and add repeaters for long or obstructed paths; bring a spare unit to use as a repeater. For the best performance, physically install the unit according to the radiation pattern shown in the images in Radio planning > Radiation pattern (section ID: radiation-pattern).

Manual section: Radio planning > Wireless design considerations / Installation Guidelines; Radio planning > Radiation pattern > Wall mount (section ID: installation-and-placement-of-wireless-devices-and-external-antennas)

See also: Radiation pattern (section ID: radiation-pattern)

W-Modbus Wall mount PRO (840-2114): Can I install the Wall mount PRO inside a metal electrical cabinet?

Also asked as:

No. The Wall mount PRO must not be installed inside a metal electrical cabinet or enclosure. Metal severely attenuates the radio signal, which drastically reduces range and link quality. Mount the Wall mount PRO outside the cabinet, ideally in open space with a clear path to neighboring nodes. If the connected device sits inside a cabinet, run the RS485 cable out to the Wall mount PRO. Where the unit must be housed inside a metal cabinet, use the DIN rail form factor with an external antenna mounted outside the enclosure. For the best performance, physically install the unit according to the radiation pattern shown in the images in Radio planning > Radiation pattern (section ID: radiation-pattern).

Manual section: Radio planning > Electrical Cabinets; Antenna Range estimates; Radio planning > Radiation pattern > Wall mount (section ID: electrical-cabinets)

See also: Radiation pattern (section ID: radiation-pattern), Wireless best practices (section ID: installation-and-placement-of-wireless-devices-and-external-antennas)

W-Modbus Wall mount PRO (840-2114): How should I position the units to get the best wireless performance?

Also asked as:

Physically install the units according to the radiation pattern shown in the images in Radio planning > Radiation pattern (section ID: radiation-pattern); this gives the best wireless performance. Placement is especially important for the Wall mount: do not install it inside a metal cabinet or enclosure, because the metal severely attenuates the radio signal strength. Mount it in open space, at least 1.5 m (5 ft) above the floor, with a clear path to neighboring nodes.

Manual section: Radio planning > Radiation pattern (section ID: radiation-pattern)

See also: Electrical Cabinets (section ID: electrical-cabinets)

Setup

W-Modbus Wall mount PRO (840-2114): What do I need before installation?

Also asked as:

Disconnect power, check Modbus RTU requirements (Application Guide) and environment (wireless design). Use shielded twisted-pair RS485 cable with 100–130 Ω impedance. Wall mount-specific: make sure the wall can support the device's weight, provide ventilation clearance and mount at an accessible height for maintenance. Follow local codes and use PPE. Do not install the Wall mount PRO inside a metal cabinet or enclosure: the metal attenuates the wireless signal and drastically reduces range. Mount it outside the cabinet and, if the connected device is inside, run the RS485 cable out to it. See Electrical Cabinets (section ID: electrical-cabinets).

Manual section: Setup Guide > Pre-installation Requirements; Radio planning > Radiation pattern > Wall mount (section ID: pre-installation-requirements)

See also: Radiation pattern (section ID: radiation-pattern), Wireless best practices (section ID: installation-and-placement-of-wireless-devices-and-external-antennas)

W-Modbus Wall mount PRO (840-2114): What are the physical installation steps?

Also asked as:

1) Check the unit for damage. 2) Mount the backplate of the enclosure on the wall. 3) Connect power and the Modbus RTU device, using the rear and/or top knockouts for cable entry. 4) Confirm the wiring is secure and the LEDs light. 5) Secure the front case to the backplate. 6) Set the gateway baud rate with the DIP switches (default 9600 baud, no parity, 1 stop bit). Do not install the Wall mount PRO inside a metal cabinet or enclosure: the metal attenuates the wireless signal and drastically reduces range. Mount it outside the cabinet and, if the connected device is inside, run the RS485 cable out to it. See Electrical Cabinets (section ID: electrical-cabinets).

Manual section: Setup Guide > Physical Setup; Radio planning > Radiation pattern > Wall mount (section ID: physical-setup)

See also: Radiation pattern (section ID: radiation-pattern), Wireless best practices (section ID: installation-and-placement-of-wireless-devices-and-external-antennas)

W-Modbus Wall mount PRO (840-2114): Where should I install the Wall mount? Can it go inside a metal cabinet?

Also asked as:

Install the Wall mount outside any metal cabinet or enclosure, ideally in open space with a clear path to neighboring nodes. Do not place it inside a metal cabinet: the metal attenuates the wireless signal and drastically reduces range and link quality. If the connected device sits inside a cabinet, run the RS485 cable out to the Wall mount. If the unit must be housed inside a metal cabinet, use the DIN rail form factor with an external antenna mounted outside the cabinet. For the best performance, physically install the unit according to the radiation pattern shown in the images in Radio planning > Radiation pattern (section ID: radiation-pattern).

Manual section: Radio planning > Electrical Cabinets (section ID: electrical-cabinets)

W-Modbus Wall mount PRO (840-2114): Should I commission with the app or without it?

Also asked as:

There are two valid ways to commission nodes to a gateway: the mobile app commissioning method and the physical commissioning method (without the app). Both work, but the mobile app method is preferred: it identifies devices, adds nodes and shows the network map; the gateway must be in secure mode. With the physical method, set the gateway to commissioning mode, let nodes join, then switch to secure. To add nodes to an existing network, use the app; putting the gateway back into commissioning mode uncommissions all existing nodes.

Manual section: Setup Guide > Commissioning procedure selector (section ID: commissioning-procedure-selector)

W-Modbus Wall mount PRO (840-2114): How do I commission nodes using the mobile app?

Also asked as:

This is the preferred of the two valid commissioning methods (the other is the physical commissioning method, without the app). Set the gateway's three-pole switch to the secure-gateway position (◼). Triple-press the gateway, open the app, tap Commission, identify and select (rename) the gateway. Nodes ship in commissioning mode (blue sweep); hold 10 s to uncommission if not. Tap Add on each node; it reboots and its top LED turns green/yellow/red. Verify the node count and network map afterwards.

Manual section: Mobile App Commissioning Method (Step-by-Step) (section ID: mobile-app-commissioning-method-stepbystep)

W-Modbus Wall mount PRO (840-2114): How do I commission without the app?

Also asked as:

This is the physical commissioning method, one of two valid ways to commission nodes; the other is the mobile app method, which is preferred. Set the gateway's three-pole switch to the commissioning position (◻). Power the nodes (blue sweep; hold 10 s if not). Each node blinks all LEDs green when it receives credentials. Confirm all devices in your controller, then switch the gateway to secure mode; nodes blink yellow and reboot. The network takes up to 15 minutes to reform.

Manual section: Physical Commissioning Method (Step-by-Step) (section ID: physical-commissioning-method-stepbystep)

W-Modbus Wall mount PRO (840-2114): How do I verify my installation is working?

Also asked as:

Gateway in secure mode with all nodes commissioned (allow up to 15 min to reform); node LEDs green or yellow, and RS485 LEDs green where Modbus RTU devices are expected; all nodes visible in the network map with PDR above 95% (no RS485 hexagon is expected on the gateway); the Modbus RTU client can read the intended Modbus RTU servers; save a network map PDF.

Manual section: Setup Guide > Installation Verification; Radio planning > Radiation pattern > Wall mount (section ID: installation-verification)

See also: Radiation pattern (section ID: radiation-pattern), Wireless best practices (section ID: installation-and-placement-of-wireless-devices-and-external-antennas)

Application

W-Modbus Wall mount PRO (840-2114): What are the recommended Modbus RTU client settings?

Also asked as:

Use a reply timeout of at least 1 second and at least 3 retries per request, and aim for PDR above 95% on all nodes. W-Modbus typically adds 50–80 ms of latency, but responses can take up to 500 ms depending on the amount of data, the device baud rate and the use of repeaters. If you have more than 25 Modbus RTU devices that need a fast response, split them across several networks. For fast-polling devices such as solar inverters, enable Solar mode.

Manual section: Application Guide > Best practice settings / Response latency (section ID: best-practice-settings)

W-Modbus Wall mount PRO (840-2114): What is Solar mode and how do I enable it?

Also asked as:

Solar mode improves compatibility with solar inverters that poll very fast (some wait 100 ms or less for a reply). It needs firmware 4.2.0 or later and the latest W-Modbus app. Connect to the gateway in the app and toggle Solar Mode on the home screen; the gateway restarts and all nodes rejoin, causing brief downtime. Connect the inverter at the Gateway and the smart meter at a Node, adding repeater nodes in between if needed. LumenRadio keeps a list of tested inverter and smart meter pairs (including Fronius, Growatt, Huawei, Kostal, SAJ, Sigenergy, Solinteg, Solis and Sungrow) but cannot guarantee compatibility. Where possible, disable automatic firmware updates on the inverter and smart meter, and raise a support ticket for untested combinations.

Manual section: Application Guide > Solar applications / Solar Inverter and Smart Meter Compatibility List; Radio planning > Solar Installations (section ID: solar-applications)

W-Modbus Wall mount PRO (840-2114): Can I monitor the wireless network from my Modbus client (remote diagnostics)?

Also asked as:

The gateway also acts as a Modbus RTU server and exposes wireless network diagnostics in holding registers, read with function code 3 (Read Holding Registers) at the default address 201. Remote diagnostics over Modbus is available only from gateway firmware 4.3.0; earlier firmware does not expose these registers, so update the gateway first. The registers must be configured manually in your Modbus client. Key registers: 30 = number of wireless nodes; 31 = number of Modbus server devices; 32–34 = firmware major/minor/patch; 35–36 = nodes that received/installed the latest firmware; 37 = Solar mode enabled; 57 = RSSI to parent; 59–60 = uptime in hours; 101–200 = PDR per node (255 = no valid link); 301–400 = parent node ID (255 = direct link to the gateway); 501–600 = RS485 bus configuration per node; 801–1800 = node names; 2000–3599 = Modbus addresses per node. Register availability depends on the gateway firmware version. On site, connect to the gateway with the W-Modbus mobile app and open the network map: the hexagon next to each node shows its PDR (packet delivery ratio), see Mobile App > Network Map > PDR (section ID: pdr).

Manual section: Remote Diagnostics > Register mapping; Release Notes > 4.3.0 (section ID: remote-diagnostics)

Remote diagnostics

W-Modbus Wall mount PRO (840-2114): How do I monitor the wireless performance of my W-Modbus network?

Also asked as:

There are two ways:

Manual section: Mobile App > Network Map > PDR (section ID: pdr); Remote Diagnostics (section ID: remote-diagnostics)

W-Modbus Wall mount PRO (840-2114): Can I see the wireless diagnostics in Niagara or another BMS?

Also asked as:

Yes. Any BMS or controller that works as a Modbus RTU client (master), such as Niagara, can read them. The gateway answers on Modbus address 201 and exposes the wireless network metrics as holding registers (function code 0x03). Remote diagnostics over Modbus is available only from gateway firmware 4.3.0; earlier firmware does not expose these registers, so update the gateway first. Add the registers you need to your Modbus client using the register map in the manual. On site, connect to the gateway with the W-Modbus mobile app and open the network map: the hexagon next to each node shows its PDR (packet delivery ratio), see Mobile App > Network Map > PDR (section ID: pdr).

Manual section: Remote Diagnostics (section ID: remote-diagnostics)

Troubleshooting

W-Modbus Wall mount PRO (840-2114): The RS485 LED is red / no RS-485 device detected. What do I do?

Also asked as:

Check RS485 polarity and the bus settings (baud rate, parity, stop bits). Make sure the Modbus RTU client (master) is connected to the W-Modbus Gateway and the servers (slaves) are connected to the nodes. In solar installations, the inverter must be connected at the Gateway and the smart meter at the Node, with the gateway in Solar mode. Confirm the Modbus RTU device itself works.

Manual section: Troubleshooting > No RS-485 device detected (section ID: no-rs-485-device-detected)

W-Modbus Wall mount PRO (840-2114): How does a node find its Modbus RTU devices, and how long does it take?

Also asked as:

Nodes scan Modbus RTU addresses 1 to 255 using the current baud rate, parity and stop bits, by requesting holding register 0 from each address with a 300 ms timeout. A device at address 255 therefore takes about 1 min 17 s to be found. The third LED blinks faster while scanning and changes from red to green once a device is found. Double-press the button to restart the scan. You can also set device addresses manually in the app (up to 4 on PRO units; clear all addresses to return to automatic assignment).

Manual section: Application Guide > Server Scanning; Mobile App > Setting Modbus Addresses (section ID: server-scanning)

W-Modbus Wall mount PRO (840-2114): Nodes aren't connecting to the gateway. What should I check?

Also asked as:

Check which of the two commissioning methods you are using – both are valid, and the mobile app method is preferred. Mobile app method: confirm the gateway is in secure mode and that you tapped Add for each node in the app. Physical method: confirm the gateway is in commissioning mode and the nodes are in commissioning mode (blue sweep). In both cases, check that nothing is still in range test mode, and that nodes are within range; move closer or add repeater nodes.

Manual section: Troubleshooting > Wireless > Nodes are not connecting (section ID: nodes-are-not-connecting-to-gateway)

W-Modbus Wall mount PRO (840-2114): Some nodes stay in secure mode after I switched the gateway back to commissioning. Why?

Also asked as:

Those nodes hadn't rejoined the gateway in time to get the instruction. Put the gateway back in secure mode for 10 minutes so all nodes rejoin, then switch to commissioning; or uncommission each node manually (hold button 10 s).

Manual section: Troubleshooting > Wireless (section ID: when-i-put-the-gateway-back-into-commissioning-mode-some-nodes-stay-in-secure-mode)

Firmware

W-Modbus Wall mount PRO (840-2114): What is the latest firmware and how do I check my version?

Also asked as:

Latest is 4.3.1 (released 2026-11-18). Check in the app, or hold the button 15 s and release on cyan: the top LED blinks the major number, the middle LED the minor and the bottom LED the patch (e.g., 3-3-2 blinks = 3.3.2).

Manual section: Firmware Updates > Checking Current Version (section ID: checking-current-version)

W-Modbus Wall mount PRO (840-2114): How do I update firmware without the W-Modbus app?

Also asked as:

The preferred way to update firmware is always through the W-Modbus app. Use the nRF Connect update flow only if the device runs firmware below 3.0.0, or as a fallback after multiple failed update attempts with the W-Modbus app: download the firmware zip from LumenRadio, install nRF Connect, hold the button for 20 s until the middle LED turns red (bootloader mode), scan and connect to the W-Modbus-DFU device, select the file via the DFU icon and wait for "Application has been sent successfully". Below 3.0.0, FOTA is not available, so every device must be updated this way. From 3.0.0 onwards, update only the gateway and FOTA updates the nodes.

Manual section: Firmware Updates > Update Procedures > nRF Connect (section ID: nrf-connect)

W-Modbus Wall mount PRO (840-2114): What changed in firmware 4.3.0 and are there known issues?

Also asked as:

Released 2026-09-07. Added: improved Solar mode compatibility, wireless network diagnostics readable over Modbus RTU, and support for the OEM Module Development Kit MK2. Changed: range test mode exits automatically after 30 minutes. Fixed: failures when fetching network information via the app, and intermittent RS485 communication failures. Known issues: bandwidth is reduced by 33% while the app is connected; downgrading below 3.0.0 factory-resets the device.

Manual section: Firmware Updates > Release Notes > 4.3.0 (section ID: 430)

Support

W-Modbus Wall mount PRO (840-2114): How long is the warranty and what voids it?

Also asked as:

Warranty length is set by your distributor, typically 1–5 years from shipment. It is void if the product is repaired or modified without LumenRadio approval, or the serial number is missing or illegible. Defects must be reported in writing within 15 days of discovery.

Manual section: Warranty and Support > Warranty Terms / Return and complaint policy (section ID: warranty-terms)

W-Modbus Wall mount PRO (840-2114): Who should I contact for support and what should I include?

Also asked as:

Contact your installer or distributor first for installation, wiring, power, configuration and warranty questions; contact LumenRadio support for firmware errors (e.g., all LEDs solid red) or unresolved issues via Create Support Ticket. Include symptoms, product/serial/firmware, controller make and model, steps tried, photos, LED video, network map PDF/PDR, power type, bus settings, wireless conditions and antennas used.

Manual section: Warranty and Support > When to Contact Support / What to include (section ID: when-to-contact-support)

W-Modbus Wall mount PRO (840-2114): How do I file an RMA?

Also asked as:

Submit an RMA claim through the LumenRadio support system with the product serial numbers, a clear fault description, and details of how the device was installed.

Manual section: Warranty and Support > RMA claims (section ID: rma-claims)

Regulatory

W-Modbus Wall mount PRO (840-2114): What certifications does the product have?

Also asked as:

CE (RED 2014/53/EU), UKCA, FCC Part 15 Class B (FCC IDs XRSTIMOMWAN301, XRSTIMOMWAN201), Industry Canada/ISED, MIC (Japan) and KC (South Korea), with 2.4 GHz approvals listed for China, India, Australia, South Africa, Malaysia and Vietnam. Keep at least 20 cm between antenna and people (FCC exposure).

Manual section: Regulatory Compliance (section ID: regulatory-compliance)

W-Modbus Wall mount PRO (840-2114): Is the W-Modbus wireless communication encrypted and secure?

Also asked as:

Yes. All data sent over the W-Modbus wireless mesh is encrypted with AES-128, and only devices with the network credentials can join the mesh. Configuration requires physical access to the device, network keys are only shared as encrypted blobs that only W-Modbus devices can decrypt, and firmware updates are signed and verified on every device.

Manual section: Security features (section ID: security-features)

W-Modbus Wall mount PRO (840-2114): Can W-Modbus be accessed or managed from the internet?

Also asked as:

No. W-Modbus devices have no Ethernet, Wi-Fi or other interface to an external IP network, no border-router function and no cloud or remote management interface. IPv6 is used only for internal addressing inside the encrypted MiraMesh network. The devices cannot be configured, managed or updated from the internet or over the Modbus interface.

Manual section: Interfaces (section ID: interfaces)

W-Modbus Wall mount PRO (840-2114): Can someone change the W-Modbus configuration over Bluetooth without physical access?

Also asked as:

No. W-Modbus devices do not advertise over Bluetooth Low Energy (BLE) by default. Press the button on the device three times to make it connectable; it then advertises for 3 minutes and stops if no connection is made. A connected session disconnects automatically after 2 minutes of inactivity. The BLE connection uses only the on-chip antenna, so you normally need to be within 2–3 m of the device.

Manual section: Configuration requires physical access (section ID: configuration-requires-physical-access)

W-Modbus Wall mount PRO (840-2114): How are W-Modbus firmware updates protected?

Also asked as:

Every firmware file is digitally signed. The update is sent from the mobile app over BLE to the gateway, which distributes it to the nodes as AES-128-encrypted mesh messages. The gateway and each node check the signature before installing; if the check fails, that device rejects the update and keeps its current firmware. Updates can only start over BLE, so they need physical access to the gateway.

Manual section: Secure firmware updates (section ID: secure-firmware-updates)

W-Modbus Wall mount PRO (840-2114): Does W-Modbus comply with the RED cybersecurity requirements (EN 18031)?

Also asked as:

LumenRadio has assessed W-Modbus as outside the scope of RED Article 3(3)(d), because it has no interface to any external IP network and cannot communicate over the internet, so no Notified Body evaluation against EN 18031-1 is required. Article 3(3)(e) does not apply because W-Modbus does not process personal data, and Article 3(3)(f) does not apply because it has no financial functions. W-Modbus still includes security measures in line with the intent of EN 18031-1.

Manual section: EU Radio Equipment Directive – Article 3(3)(d), (e), (f) (section ID: eu-radio-equipment-directive-article-33d-e-f)

W-Modbus Wall mount PRO (840-2114): What is the system integrator responsible for to keep a W-Modbus installation secure?

Also asked as:

Secure the Modbus master (BMS, SCADA system or controller) with access control, strong passwords and up-to-date software; install the devices where unauthorized people can't easily reach them, such as locked cabinets or plant rooms; keep the firmware up to date through the mobile app; and treat Modbus as unauthenticated by restricting who and what can reach the Modbus master.

Manual section: Responsibilities of the system integrator (section ID: responsibilities-of-the-system-integrator)

W-Modbus Wall mount PRO (840-2114): How do I report a security vulnerability in W-Modbus?

Also asked as:

Submit a request through the LumenRadio support portal. Include the product name, firmware version and a description of the issue, and do not disclose the vulnerability publicly until LumenRadio has had the chance to investigate and respond.

Manual section: Reporting security issues (section ID: reporting-security-issues)