W-Modbus PRO module (840-2115) customer Q&A

Every answer on this page applies only to the W-Modbus PRO module (SKU 840-2115, Modbus RTU). Do not use these answers for other LumenRadio products or form factors. Full manual: W-Modbus PRO module manual

Firmware

W-Modbus PRO module (840-2115): What changed in firmware 4.3.0 and are there known issues?

Also asked as:

Released 2026-09-07. Added: improved Solar mode compatibility, wireless network diagnostics readable over Modbus RTU, and support for the OEM Module Development Kit MK2. Changed: range test mode exits automatically after 30 minutes. Fixed: failures when fetching network information via the app, and intermittent RS485 communication failures. Known issues: bandwidth is reduced by 33% while the app is connected; downgrading below 3.0.0 factory-resets the device.

Manual section: Firmware Updates > Release Notes > 4.3.0 (section ID: 430)

Support

W-Modbus PRO module (840-2115): How long is the warranty and what voids it?

Also asked as:

Warranty length is set by your distributor, typically 1–5 years from shipment. It is void if the product is repaired or modified without LumenRadio approval, or the serial number is missing or illegible. Defects must be reported in writing within 15 days of discovery.

Manual section: Warranty and Support > Warranty Terms / Return and complaint policy (section ID: warranty-terms)

W-Modbus PRO module (840-2115): How do I file an RMA?

Also asked as:

Submit an RMA claim through the LumenRadio support system with the product serial numbers, a clear fault description, and details of how the device was installed.

Manual section: Warranty and Support > RMA claims (section ID: rma-claims)

OEM module

W-Modbus PRO module (840-2115): What is the W-Modbus PRO module and what is it used for?

Also asked as:

The W-Modbus PRO module (840-2115) is a surface-mounted radio module that you integrate into your own product. It replaces the Modbus control cable with a wireless MiraMesh network in the 2.4 GHz ISM band. A network has one gateway and up to 100 mesh nodes. The module measures 18.5 mm × 33.5 mm, has a U.FL/I-PEX antenna connector, and is configured through SPI or UART.

Manual section: Product Overview (section ID: product-overview)

W-Modbus PRO module (840-2115): How is the W-Modbus PRO module delivered and how do I order it?

Also asked as:

The W-Modbus PRO module has order code 840-2115 and is delivered on reels of 400 pieces. A W-Modbus Development Kit is available for evaluation and prototyping.

Manual section: Ordering Information (section ID: ordering-information)

W-Modbus PRO module (840-2115): What power supply does the W-Modbus module need?

Also asked as:

The module runs on 3.3 V (3.0–3.6 V). Plan for 150 mA typical and 250 mA peak current during radio transmission, with a current slew rate of up to 300 A/s. Decouple the supply pin with a 100 nF ceramic capacitor close to the pin, and add a bulk ceramic capacitor such as 47 µF. Do not apply a voltage to any pin before the 3.3 V rail is connected.

Manual section: Power Supply Recommendations (section ID: power-supply-recommendations)

W-Modbus PRO module (840-2115): How do I connect an RS485 transceiver to the W-Modbus module?

Also asked as:

Connect the RS485 driver to UART_TXD (P8), UART_RXD (P15), RS485_DE (P10) and RS485_RE (P11). The voltage on UART_RXD must not exceed VDD (3.3 V), so a 5 V driver needs a level-shifting circuit, such as a resistor divider, on its RX output. The manual includes an RS485 reference design.

Manual section: RS485 Interface (section ID: rs485-interface)

W-Modbus PRO module (840-2115): Should I use the SPI or the UART interface to configure the module?

Also asked as:

Use either one; both management interfaces have the same capabilities. SPI is register-based with an interrupt (IRQ) signal, and UART uses text commands such as r:APP_MODE. Both are ready 1500 ms after the module starts booting.

Manual section: Management Interfaces (section ID: management-interfaces)

W-Modbus PRO module (840-2115): What are the UART settings of the module's management interface?

Also asked as:

Use 115200 baud, no parity and 1 stop bit, and end every command with \r\n. Keep at least 100 ms of silence between frames, and wait 1500 ms after boot before sending commands. The UART management interface requires firmware 3.2.0 or later.

Manual section: UART Configuration (section ID: uart-configuration)

W-Modbus PRO module (840-2115): What SPI mode and clock speed does the module support?

Also asked as:

The maximum SPI clock is 4 MHz, data is valid on the rising edge of SCK, data is sent most significant bit first, and multi-byte registers are big-endian. Each command is two transactions: wait for the IRQ pin to go low before sending the second one. A reset of the SPI master or glitches on CS can make the module unresponsive for 5 seconds.

Manual section: Maximum Clock Speed (section ID: maximum-clock-speed)

W-Modbus PRO module (840-2115): How do I commission a network of W-Modbus modules?

Also asked as:

Set the module at the Modbus controller/client to Commissioning Gateway mode (APP_MODE 2) and the other modules to Commissioning Mesh mode (APP_MODE 4, the default). When COMMISSIONING reads 1, a node has joined, usually within about a minute. Then set the gateway to Secure Gateway mode (APP_MODE 1); all modules restart synchronously after 10 seconds and the network runs encrypted.

Manual section: Commissioning (section ID: commissioning)

W-Modbus PRO module (840-2115): How do I factory reset or decommission a W-Modbus module?

Also asked as:

Write 1 to DEVICE_RESET to factory reset a module; it restarts twice and ends up in Commissioning Mesh mode. To decommission the whole network, switch the Secure Gateway to any other app mode; the connected nodes restart after 10 seconds in Commissioning Mesh mode.

Manual section: Decommissioning (section ID: decommissioning)

W-Modbus PRO module (840-2115): How does the W-Modbus module find the Modbus devices connected to it?

Also asked as:

A W-Modbus mesh node scans addresses 1–247 (1–255 in Solar mode) by reading holding register 0, and supports up to 16 devices. The scan repeats, from every minute up to every 16 minutes. Read the found addresses from SERVER_ADDRESSES after a full scan cycle. Writing addresses to SERVER_ADDRESSES stops scanning and bridges only those addresses; a rescan starts scanning again.

Manual section: Detection of Connected Devices (section ID: detection-of-connected-devices)

W-Modbus PRO module (840-2115): What communication timeouts should I use with the W-Modbus module?

Also asked as:

Allow about 50 ms of round-trip latency per hop from the gateway; a node 3 hops away can add about 150 ms compared with a cable. Set the communication timeouts of your Modbus equipment to at least 1000 ms.

Manual section: Networking and Latency (section ID: networking-and-latency)

W-Modbus PRO module (840-2115): Which antennas can I use with the W-Modbus module?

Also asked as:

An external antenna is required, connected to the U.FL/I-PEX connector, with 50 ohm impedance at 2.45 GHz. The module is FCC and IC approved with these antennas or electrical equivalents: LumenRadio 2.15 dBi dipole (104-1001), Molex 3.2 dBi flex (104-1008), Microchip 0.56 dBi whip (104-1034) and LumenRadio 5 dBi puck (104-1033). The TE Connectivity dome antennas (104-1027, 104-1023) are not approved for North America. In Europe, the output power must not exceed 20 dBm. Consider the radiation pattern of the antenna, and keep the antenna clear of metal and ground planes.

Manual section: Recommended Antennas (section ID: recommended-antennas)

W-Modbus PRO module (840-2115): What should I consider in the PCB layout for the W-Modbus module?

Also asked as:

Use solid ground planes and low-impedance power paths, keep the top layer under the module free of copper (see the keep-out area), filter the supply, and check for disturbances on the 2.45 GHz band with a near-field probe. Connect all ground pins, keep the programming pins (P20, P21) accessible, and make sure the enclosure does not block the radio signal.

Manual section: Carrier Board Layout Guidelines (section ID: carrier-board-layout-guidelines)

W-Modbus PRO module (840-2115): Where can I download footprints and 3D models for the W-Modbus module?

Also asked as:

Symbols, footprints, drawings and 3D models in .stp and .dxf format are available on the W-Modbus OEM module support page linked in the manual.

Manual section: Design Files (section ID: design-files)

W-Modbus PRO module (840-2115): What reflow profile should I use for the W-Modbus module?

Also asked as:

The module complies with J-STD-020D1. Keep the absolute peak temperature at or below 260 °C for at most 5 seconds, the target reflow range at 225–250 °C, and the time above liquidus (218 °C for SAC305) at 50–70 seconds. You choose the solder paste and must make sure the oven profile matches it.

Manual section: Reflow Soldering Specification (section ID: reflow-soldering-specification)

W-Modbus PRO module (840-2115): How do I update the firmware of the W-Modbus module?

Also asked as:

From firmware 3.1.0, enable Bluetooth by writing 1 to BLUETOOTH_ENABLED and update the module with the W-Modbus app within 3 minutes; updating a gateway updates the whole network. Alternatively, enter bootloader (DFU) mode by writing 1 to BOOTLOADER_ENABLED, or by holding the BOOTLOADER pin low during a reset, and update with nRF Connect and the firmware zip file.

Manual section: Firmware Update (section ID: firmware-update)

W-Modbus PRO module (840-2115): Can I use the module's FCC ID in my product?

Also asked as:

Yes. The module carries an FCC modular grant, so the host product does not need additional testing or authorization for the module's transmitter, and can use the module's FCC ID. A label with the module's FCC ID must be visible on the host product. You remain responsible for other compliance testing of your product, such as CE, UL or CSA.

Manual section: FCC and Industry Canada Marking (section ID: fcc-and-industry-canada-marking)

W-Modbus PRO module (840-2115): Who should I contact for help with the W-Modbus module and what should I include?

Also asked as:

Contact LumenRadio support via Create Support Ticket when an issue remains after you have checked the integration guidelines and known compatibility issues, or for advice on design verification, production testing and compliance. Include symptoms, product, serial number and firmware version, the connected Modbus equipment, the steps you have tried, schematics and PCB layout of the carrier board, the values read from the management interface (APP_MODE, NETWORK_STATUS, RS485_CONFIG), the power supply design, serial bus settings, wireless conditions and the antenna used.

Manual section: When to Contact Support (section ID: when-to-contact-support)

W-Modbus PRO module (840-2115): Is the W-Modbus module's wireless communication encrypted and secure?

Also asked as:

Yes. All data sent over the W-Modbus wireless mesh is encrypted with AES-128, once the gateway has been set to Secure Gateway mode at the end of commissioning. The module has no Ethernet, Wi-Fi or other interface to an external IP network and no cloud or remote management interface; IPv6 is used only inside the encrypted mesh. Its wireless mesh network settings are configured only by the host product over the SPI or UART pins, and firmware updates are signed and verified on every device, including updates with nRF Connect.

Manual section: Security features (section ID: security-features)

W-Modbus PRO module (840-2115): How is Bluetooth on the W-Modbus module protected?

Also asked as:

The module does not advertise over Bluetooth Low Energy (BLE) by default. Only the host product can make it connectable, by setting BLUETOOTH_ENABLED in the SPI or UART management interface; the module then advertises for 3 minutes and stops if no connection is made. Bootloader (DFU) mode is only entered when the host product sets BOOTLOADER_ENABLED or drives the BOOTLOADER pin low during a reset, and the module returns to application mode after 2 minutes without BLE activity.

Manual section: Configuration controlled by the host product (section ID: configuration-controlled-by-the-host-product)

W-Modbus PRO module (840-2115): Does the W-Modbus module comply with the RED cybersecurity requirements (EN 18031)?

Also asked as:

LumenRadio has assessed the W-Modbus module as outside the scope of RED Article 3(3)(d), so no Notified Body evaluation against EN 18031-1 is required. The module has no interface to any external IP network and exposes no IP interface to the host product either, so it cannot connect to the internet in any form. Article 3(3)(e) does not apply because the module does not process personal data, and Article 3(3)(f) does not apply because it has no financial functions. If your host product has its own internet connection, the host product is the internet-facing equipment and is responsible for network protection on the IP side.

Manual section: EU Radio Equipment Directive – Article 3(3)(d), (e), (f) (section ID: eu-radio-equipment-directive-article-33d-e-f)

W-Modbus PRO module (840-2115): How do I keep my product with the W-Modbus module secure?

Also asked as:

The wireless mesh network settings of the module can be configured over its SPI or UART pins, so it is your responsibility as the OEM vendor to design the host product with security in mind. Expose only non-sensitive items, such as status and diagnostics, remotely, and protect any remote access with access control, strong passwords and up-to-date software. Writing parameters to the module, such as changing the app mode, resetting it or enabling Bluetooth or bootloader mode, should require physical access to the host product. Enable Bluetooth and bootloader mode only when needed, and do not make the BOOTLOADER and nRESET pins accessible from outside the product. Set the gateway to Secure Gateway mode when commissioning is finished, keep the firmware up to date, and treat Modbus as unauthenticated by restricting who and what can reach the Modbus network.

Manual section: Responsibilities of the host product manufacturer (section ID: responsibilities-of-the-host-product-manufacturer)

W-Modbus PRO module (840-2115): How do I report a security vulnerability in the W-Modbus module?

Also asked as:

Submit a request through the LumenRadio support portal. Include the product name, firmware version and a description of the issue, and do not disclose the vulnerability publicly until LumenRadio has had the chance to investigate and respond.

Manual section: Reporting security issues (section ID: reporting-security-issues)