W-Modbus Compact (840-2130) customer Q&A
Every answer on this page applies only to the W-Modbus Compact (SKU 840-2130, Modbus RTU). Do not use these answers for other LumenRadio products or form factors. Full manual: W-Modbus Compact manual
Product overview
W-Modbus Compact (840-2130): What is W-Modbus Compact and what does it do?
Also asked as:
- What is the W-Modbus Compact used for?
- Can you give me an overview of the W-Modbus Compact?
- How does the W-Modbus Compact work?
W-Modbus replaces the RS485 control cable in a Modbus RTU installation with a wireless mesh link, removing the need for daisy-chaining, cable planning and cable troubleshooting while keeping standard Modbus RTU compatibility. The Compact is the smallest W-Modbus form factor and can only be used as a mesh Node, connected to one or more Modbus RTU servers. W-Modbus is built on LumenRadio's MiraOS, which runs the MiraMesh network stack.
Manual section: Introduction > Product Overview (section ID: product-overview)
W-Modbus Compact (840-2130): How many devices can a W-Modbus network support?
Also asked as:
- What is the maximum number of nodes in a W-Modbus network?
- How many devices can I connect to one gateway?
- Is there a limit on network size?
A W-Modbus network supports up to 100 mesh nodes per gateway, although the recommended size may be lower depending on the radio environment and network topology. Each Compact node supports 1 local Modbus RTU server device. The Modbus RTU client is always connected at the gateway. If you have more than 25 Modbus RTU devices that require a fast response rate, split the system into two or more networks.
W-Modbus Compact (840-2130): Is there a PRO version of the Compact?
Also asked as:
- Does the Compact come in a PRO version?
- Can the Compact connect up to 4 devices?
- Is there a Compact PRO?
No. The Compact has no PRO variant. PRO versions, which support up to 4 connected local Modbus RTU devices when used as a mesh node (versus 1 on the standard units), are only available for the DIN rail and Wall mount form factors.
Manual section: Introduction > Glossary of Terms (section ID: glossary-of-terms)
W-Modbus Compact (840-2130): What is the difference between a Gateway and a Node?
Also asked as:
- Should my device be a gateway or a node?
- What role does the gateway play compared to a node?
- Where do I connect the controller – to the gateway or a node?
The Gateway is the central root device of the network, and all wireless unicast messages pass through it. The Modbus RTU client (master) must be connected to the Gateway to query devices on the nodes. Nodes connect to Modbus RTU servers (slaves), and every node also acts as a repeater automatically, even with no Modbus device connected. Use only one Gateway per network; choose a DIN rail or Wall mount as the Gateway. Any form factor (Compact, DIN rail, DIN rail PRO, Wall mount or Wall mount PRO) can be a node.
Manual section: Glossary of Terms; System Description > W-Modbus Mesh Network; Radio planning > Gateway & Node selection (section ID: gateway-node-selection)
Safety
W-Modbus Compact (840-2130): What safety precautions apply when installing the device?
Also asked as:
- Are there any safety warnings for installation?
- What do I need to know about electrical safety?
- Who is allowed to install the device?
Disconnect power before wiring, verify the supply matches spec and check DC polarity, use correctly rated wiring and overcurrent protection, follow local electrical codes, use ESD protection, and have only qualified technicians install it. Do not install in wet locations or above 95% RH, do not use if damaged, and do not use for safety-critical tasks.
Manual section: Safety Information; Warnings and Precautions (section ID: safety-information)
W-Modbus Compact (840-2130): What should I watch out for when sharing a power supply with other devices?
Also asked as:
- Can I use the same transformer for this device and other equipment?
- Can I share a 24 VAC transformer with other devices?
- What is the half-wave rectified circuit caution?
W-Modbus uses a half-wave rectified circuit, so it should not share a VAC transformer with a device that uses a full-wave rectified circuit. A shared transformer is only acceptable if the other devices are also half-wave rectified and all power connections have the same polarity: the W-Modbus "+" terminal must never be connected to the "–" terminal of another device. When connecting a 24 V isolation transformer, follow IEC 61558-1.
Manual section: Safety Information > Electrical Safety / Power and RS485 Circuit Caution (section ID: power-and-rs485-circuit-caution)
Specifications
W-Modbus Compact (840-2130): What are the power requirements?
Also asked as:
- What voltage does the device need?
- Can I power it with 12 V or 24 V, AC or DC?
- How much power does the device consume?
24 VAC ±10% or 12–24 VDC ±10%. Maximum consumption is 0.8 W (average 0.45 W); there is no 24 V throughput power. Troubleshooting guidance asks for a supply that can deliver at least 0.5 A.
Manual section: Device Overview > Specifications; Troubleshooting > None of the LEDs are blinking (section ID: specifications)
W-Modbus Compact (840-2130): What are the physical and environmental specs of the Compact unit?
Also asked as:
- What are the dimensions and weight of the Compact?
- What temperature and humidity range is the Compact rated for?
- What IP rating does the Compact have?
48 × 85 × 22 mm, 55 g, IP40, internal antenna. Operating temperature −20 °C to +55 °C (−4 °F to 131 °F), storage −30 °C to +80 °C, humidity 10–95% non-condensing. Terminals accept 0.2–1.5 mm² conductors (AWG 24–16).
Manual section: Device Overview > Specifications (section ID: specifications)
W-Modbus Compact (840-2130): What radio frequency and output power does it use?
Also asked as:
- What frequency band does it operate on?
- What is the maximum transmit power?
- Does it use 2.4 GHz?
2402–2480 MHz (2.4 GHz band) with maximum RF output power of 100 mW. Network traffic is encrypted with AES-128 using credentials unique to each gateway.
Manual section: Device Overview > Specifications; System Description > W-Modbus Mesh Network (section ID: specifications)
W-Modbus Compact (840-2130): Does the Compact have a termination resistor, and can I disable it?
Also asked as:
- Does the Compact have a built-in EOL resistor?
- Can I turn off the 120 Ω termination on the Compact?
- Where should the Compact be placed on the RS485 trunk?
Yes, it has a built-in 120 Ω end-of-line resistor that cannot be disabled. Place the unit at one end of the RS485 trunk and terminate the other end with a 120 Ω resistor (built-in or external).
Manual section: Setup Guide > Wiring > Wiring Diagram; Troubleshooting > Can the EOL resistor be disabled? (section ID: wiring-diagram)
Device overview
W-Modbus Compact (840-2130): What are the physical components on the device?
Also asked as:
- What are the parts on the device?
- What connectors and switches does the device have?
- Can you describe the device layout?
The Compact is the smallest W-Modbus form factor. It is configured using a single push button and has no DIP switches or three-pole mode switch, so its bus settings always come from the gateway.
Manual section: Introduction > Glossary of Terms (section ID: device-overview)
System
W-Modbus Compact (840-2130): What is the difference between commissioning mode and secure mode?
Also asked as:
- What does commissioning mode mean?
- What is secure mode?
- When does the network switch from commissioning to secure mode?
Commissioning mode uses known, shared credentials so new nodes can find and join a gateway. When the gateway is switched to secure mode, all nodes reboot together and switch to encrypted credentials unique to that gateway for long-term operation, so nearby networks don't interfere.
Manual section: System Description > Commissioning Network / Secure Network (section ID: commissioning-network)
W-Modbus Compact (840-2130): How does the gateway share its serial settings with nodes?
Also asked as:
- Do nodes use the gateway's baud rate?
- What is config distribution?
- Can a node use its own serial settings instead of the gateway's?
The gateway distributes its bus settings (baud rate, parity and stop bits) to all nodes. The Compact has no DIP switches, so it always uses the bus settings it receives from the gateway.
Manual section: System Description > Config Distribution; Setup Guide > Set the baud rate on the Gateway (section ID: config-distribution)
W-Modbus Compact (840-2130): What is FOTA and do I need to update every node?
Also asked as:
- How do firmware updates reach the nodes?
- Do I have to update each node separately?
- What is firmware over the air?
Firmware-Over-The-Air (from FW 3.0.0) lets the gateway push new firmware to every node in a secure network automatically. Update only the gateway, preferably through the W-Modbus app; propagation typically takes 30 minutes to 2 hours depending on network size. Progress is shown via FOTA Status in the app. If the devices run firmware below 3.0.0, FOTA is not available and they must be updated using the nRF Connect update flow.
Manual section: System Description > FOTA; Mobile App > Complete update / FOTA status (section ID: firmware-over-the-air-fota)
Accessories
W-Modbus Compact (840-2130): What accessories are available for the Compact?
Also asked as:
- Which accessories can I buy for the Compact?
- Is there an outdoor kit or extra antenna for the Compact?
- What add-ons are available for the Compact?
The accessories in the manual (outdoor kit, IP67 enclosure, external antennas, antenna cables, DIN rail power supply and outer shell) are designed for the DIN rail form factor. Only the DIN rail supports external antennas, so these do not apply to the Compact. Check with your distributor for accessories available for the Compact.
Manual section: DIN Rail Accessories > Available Accessories (section ID: specifications)
W-Modbus Compact (840-2130): How do I install W-Modbus outdoors?
Also asked as:
- Can I use W-Modbus outside?
- Is there an outdoor kit?
- What enclosure do I need for an outdoor installation?
Place the device in a suitably rated IP enclosure to protect it from dust and moisture, and mount it where snow cannot build up around it. The DIN Outdoor Kit (800-2324) is designed for the DIN rail form factor. The Compact must not be installed in a metal enclosure; where a metal enclosure is required, use a DIN rail unit with its antenna mounted outside the enclosure.
Manual section: Radio planning > Outdoor Installations; Radio planning > Radiation pattern > Compact (section ID: outdoor-installations)
See also: Radiation pattern (section ID: radiation-pattern), Wireless best practices (section ID: installation-and-placement-of-wireless-devices-and-external-antennas)
W-Modbus Compact (840-2130): Can I use a third-party antenna?
Also asked as:
- Can I use my own antenna?
- Which antennas are compatible?
- Can I replace the stock antenna with a different one?
No. Only the DIN rail supports external antennas; the Compact uses its built-in antenna. If your installation needs an external or high-gain antenna, use a DIN rail unit.
Manual section: Radio planning > Wireless design considerations (section ID: specifications)
W-Modbus Compact (840-2130): Which antenna setup should I choose?
Also asked as:
- Which antenna should I use for my installation?
- How do I pick the right antenna and cable?
- Which antenna option is best for a metal enclosure?
- Which antenna SKUs or part numbers do I need?
- How do I choose an antenna that suits my application?
The antenna options in the manual (external omni antenna, long cable, puck antenna and directional antenna) apply only to the DIN rail. The Compact uses its built-in antenna, so focus on placement: mount it at least 1.5 m above the floor, keep it clear of metal and obstructions, and never install it inside a metal cabinet or enclosure. For the best performance, physically install the unit according to the radiation pattern shown in the images in Radio planning > Radiation pattern (section ID: radiation-pattern).
See also: Radiation pattern (section ID: radiation-pattern), Wireless best practices (section ID: installation-and-placement-of-wireless-devices-and-external-antennas)
W-Modbus Compact (840-2130): What range can I expect with each antenna?
Also asked as:
- How far apart can the devices be?
- What is the wireless range?
- What distance can I get with an external antenna?
The range estimates in the manual (up to 600 m line of sight) are for the DIN rail and its external antenna accessories. Range for the Compact depends on placement and surroundings, and is lower where walls, metal and other obstructions are present. Use the radiation pattern and LumenRadio's wireless range calculator to plan, and run a range test to confirm. Do not install the Compact inside a metal cabinet or enclosure, as the metal severely attenuates the signal.
See also: Radiation pattern (section ID: radiation-pattern), Wireless best practices (section ID: installation-and-placement-of-wireless-devices-and-external-antennas)
W-Modbus Compact (840-2130): How do I swap or fit an external antenna?
Also asked as:
- How do I change the antenna?
- How do I connect an external antenna?
- Can I replace the antenna myself?
This does not apply to the Compact: only the DIN rail supports external antennas.
Manual section: Radio planning > Wireless design considerations; Radio planning > Radiation pattern > Compact (section ID: specifications)
See also: Radiation pattern (section ID: radiation-pattern), Wireless best practices (section ID: installation-and-placement-of-wireless-devices-and-external-antennas)
LEDs
W-Modbus Compact (840-2130): What do the LED patterns mean?
Also asked as:
- What do the LED colors mean?
- How do I read the status LEDs?
- What does a blinking blue, green or yellow LED mean?
Read the LEDs left to right. Blue sweep = node in commissioning mode; green sweep = gateway in commissioning mode; all blink green = network found; all blink yellow = restarting; all solid red = firmware error (contact support); all blink white = identify. Gateway in secure mode: first LED solid magenta, and the third (RS485) LED blinks green for valid RS485 traffic, red for invalid traffic, and is off when there is no traffic. Node connected: first LED green/yellow/red shows signal strength, and the middle LED blinks green when receiving and blue when transmitting. Node connecting: first LED blinks yellow.
Manual section: LED Status Indicators > LED Pattern Descriptions (section ID: led-pattern-descriptions)
W-Modbus Compact (840-2130): What does the third (RS485) LED tell me?
Also asked as:
- What does the RS485 status LED show?
- Why is the third LED green or red?
- How can I tell if a device is detected on the bus?
On a node, it blinks green (1 s on, 4 s off) when a Modbus RTU device is found and red when none is found. A faster red blink (0.5 s on/off) means the node is scanning for Modbus RTU devices. On the gateway, it blinks green when valid RS485 traffic is received, red when invalid traffic is received, and stays off when there is no bus traffic.
Manual section: LED Status Indicators > LED Pattern Descriptions (section ID: led-pattern-descriptions)
W-Modbus Compact (840-2130): Why did the LEDs turn off?
Also asked as:
- Why are the LEDs no longer on?
- How do I keep the LEDs on permanently?
- Do the LEDs switch off automatically?
LEDs switch off after 30 minutes by default. A single press extends them by 30 minutes; holding the button 5 s (release on magenta) sets them to always on. Since FW 4.2.1 LEDs stay on if an issue is being indicated.
Manual section: LED Status Indicators; Button Functionality (section ID: led-status-indicators)
Button
W-Modbus Compact (840-2130): What does each button press do?
Also asked as:
- What are the button functions?
- What happens if I press the button twice or three times?
- What does holding the button down do?
Single press: keeps the LEDs on for 30 more minutes. Double press: rescans for Modbus RTU devices (the third LED blinks faster while scanning). Triple press: Bluetooth/app mode for 3 minutes (middle LED flashes blue twice). Hold and release on color: 5 s magenta = LEDs always on; 10 s blue = uncommission; 15 s cyan = show firmware version; 20 s red = firmware update (bootloader) mode.
Manual section: Button Functionality (section ID: button-functionality)
W-Modbus Compact (840-2130): How do I factory-reset / uncommission a node?
Also asked as:
- How do I reset a node?
- How do I remove a node from a network?
- How do I put a device back into commissioning mode?
Hold the button for 10 seconds and release when the middle LED shows blue. The device returns to commissioning mode (blue sweep) ready to join a new network. Nodes can also be removed via the app's commissioning screen.
Manual section: Button Functionality > Held button behavior; Mobile App > Removing Commissioned Devices (section ID: held-button-behavior)
Mobile app
W-Modbus Compact (840-2130): What can the W-Modbus mobile app do and what do I need?
Also asked as:
- What can I do with the W-Modbus app?
- What are the requirements for the mobile app?
- How do I connect to a device with the app?
Update firmware, diagnose the network (network map, PDR, range test, diagnostics), show device information, commission nodes, set Modbus addresses, enable Solar mode and replace gateways. You need Bluetooth on, the device powered and within range, and internet access to download firmware. Triple-press the device button to make it connectable for 3 minutes. Use the W-Modbus app: it is separate from the W-BACnet app. While the app is connected, the device has 33% less bandwidth for network traffic.
Manual section: Mobile App > Features / Requirements / Device Connection (section ID: mobile-app)
W-Modbus Compact (840-2130): How do I read the network map?
Also asked as:
- What does the network map show?
- How do I see which nodes are connected?
- What do the colors in the network map mean?
It shows a tree of the gateway and its nodes (children indented under parents). The hexagon to the left of each name shows PDR: green ≥ 99%, amber 94–99%, red < 94%. The RS485 hexagon is green if a local device is connected (red if not), and the Modbus addresses of the connected devices are shown bottom-left. The gateway has no RS485 hexagon, because it acts as the Modbus RTU client. Use Identify (LEDs blink white) and Rename (ASCII, max 8 characters).
Manual section: Mobile App > Network Map (section ID: network-map-overview)
W-Modbus Compact (840-2130): Why are some PDR values missing in the network map?
Also asked as:
- Why does a node show no PDR?
- Why is the PDR blank in the network map?
- Why does a node show limited information in the map?
Nodes may not yet have calculated and sent a PDR to the gateway, or they run firmware older than 3.0.0, which only shows limited information.
Manual section: Mobile App > Network Map > Missing PDR values (section ID: missing-pdr-values)
W-Modbus Compact (840-2130): How do I generate a network map PDF report and why should I?
Also asked as:
- How do I export the network map?
- How do I create an installation report?
- Why do I need to save the network map PDF?
Connect to the gateway, open the network map, select Generate PDF report, optionally add company and installer names, then save or share. Always keep it: it contains the recovery information required to replace a gateway, and support asks for it.
Manual section: Mobile App > PDF Report Generation; Gateway Replacement (section ID: pdf-report-generation)
W-Modbus Compact (840-2130): How do I run a range test?
Also asked as:
- How do I test signal strength between two devices?
- What is range test mode?
- How do I check the wireless link before installing?
Requires FW 4.2.1+ and a commissioned network. In the app, connect to the gateway > Settings > Range Test > toggle on, then do the same on the node. LED 1 shows PDR and LED 3 latency (green good, yellow fair, red weak). Modbus RTU traffic is blocked during the test; disable it on both node and gateway afterwards (auto-exits after 30 min from FW 4.3.0).
Manual section: Mobile App > Range Test Mode; Release Notes 4.3.0 (section ID: range-test-mode)
W-Modbus Compact (840-2130): How do I get diagnostics from a device for support?
Also asked as:
- How do I retrieve device diagnostics in the app?
- What information should I collect for support?
- Where are the diagnostics in the app?
Connect to the device in the app, tap the Settings icon, choose Diagnostics, then tap Get Diagnostics.
Manual section: Mobile App > Device Diagnostics (section ID: how-to-retrieve-diagnostics)
W-Modbus Compact (840-2130): How do I set Modbus addresses manually?
Also asked as:
- Can I assign Modbus addresses myself?
- How do I change a device's Modbus address in the app?
- How do I go back to automatic address assignment?
Modbus addresses are found automatically: each node scans for its connected Modbus RTU devices. To set them manually, connect to the node with the W-Modbus app, tap Set Address Info, enter the address and tap Update Address. The Compact supports 1 local device, so enter a single address. To return to automatic address assignment, clear all specified addresses.
Manual section: Mobile App > Setting Modbus Addresses (section ID: setting-modbus-addresses)
W-Modbus Compact (840-2130): How do I install beta firmware?
Also asked as:
- How do I switch to the beta update channel?
- How do I get beta firmware?
- How do I enable beta mode in the app?
When the app starts, tap the LumenRadio logo 8 times and select Beta mode. "Beta Mode" appears in red in the top-right corner.
Manual section: Mobile App > Switching Update Channel (section ID: switching-update-channel)
W-Modbus Compact (840-2130): The app firmware update failed. What should I do?
Also asked as:
- Why did my firmware update fail?
- The app update is stuck – what now?
- What should I do if the update shows an error?
Make sure the device is in range and connected; if it still fails, restart both the app and the W-Modbus device and try again. The W-Modbus app is always the preferred update method. If the update still fails after multiple attempts with the W-Modbus app, use the nRF Connect update flow as a fallback (this flow is also required for devices running firmware below 3.0.0).
Manual section: Mobile App > Mobile App Troubleshooting (section ID: mobile-app-troubleshooting)
Gateway replacement
W-Modbus Compact (840-2130): How do I replace a broken gateway without recommissioning?
Also asked as:
- How do I replace a faulty gateway?
- My gateway is broken – do I have to recommission all nodes?
- What is gateway replacement?
The gateway is always a Wall mount or DIN rail unit (the Compact can't be a gateway), so this applies to that unit; Compact nodes don't need recommissioning. Use Gateway Replacement in the app (Settings > Gateway Replacement). You must have the recovery info from a previously saved Network Map PDF (import the PDF, scan its QR code, or type the 32 recovery numbers). Power off the old gateway permanently, power on the new one, triple-press it, select and identify it in the app to complete. Without saved recovery info, recovery isn't possible.
Manual section: Mobile App > Gateway Replacement (section ID: gateway-replacement)
Radio planning
W-Modbus Compact (840-2130): Where should I place devices and antennas for best signal?
Also asked as:
- How high should I mount the device?
- What are the best practices for antenna placement?
- How do I get the best wireless signal?
Keep ~3/4 inch clearance around the antenna, mount at least 1.5 m (5 ft) above the floor, never install the Compact inside a metal cabinet or enclosure, keep it clear of surrounding metal, and keep outdoor antennas clear of snow. Avoid bottleneck nodes and add repeaters for long or obstructed paths; bring a spare unit to use as a repeater. For the best performance, physically install the unit according to the radiation pattern shown in the images in Radio planning > Radiation pattern (section ID: radiation-pattern).
See also: Radiation pattern (section ID: radiation-pattern)
W-Modbus Compact (840-2130): Can I install the Compact inside a metal electrical cabinet?
Also asked as:
- Will the Compact work inside a metal enclosure?
- Can I mount the Compact in a steel cabinet?
- What should I do if the Compact has to go in a metal cabinet?
No. The Compact must not be installed inside a metal electrical cabinet or enclosure. Metal severely attenuates the radio signal, which drastically reduces range and link quality. Mount the Compact outside the cabinet, ideally in open space with a clear path to neighboring nodes. If the connected device sits inside a cabinet, run the RS485 cable out to the Compact. Where the unit must be housed inside a metal cabinet, use the DIN rail form factor with an external antenna mounted outside the enclosure. For the best performance, physically install the unit according to the radiation pattern shown in the images in Radio planning > Radiation pattern (section ID: radiation-pattern).
Manual section: Radio planning > Electrical Cabinets; Antenna Range estimates; Radio planning > Radiation pattern > Compact (section ID: electrical-cabinets)
See also: Radiation pattern (section ID: radiation-pattern), Wireless best practices (section ID: installation-and-placement-of-wireless-devices-and-external-antennas)
W-Modbus Compact (840-2130): How should I position the units to get the best wireless performance?
Also asked as:
- Does the mounting direction of the unit matter?
- How do I use the radiation pattern when installing the units?
- Where is the best place to mount the unit?
- How should I orient the antenna?
Physically install the units according to the radiation pattern shown in the images in Radio planning > Radiation pattern (section ID: radiation-pattern); this gives the best wireless performance. Placement is especially important for the Compact: do not install it inside a metal cabinet or enclosure, because the metal severely attenuates the radio signal strength. Mount it in open space, at least 1.5 m (5 ft) above the floor, with a clear path to neighboring nodes.
Manual section: Radio planning > Radiation pattern (section ID: radiation-pattern)
See also: Electrical Cabinets (section ID: electrical-cabinets)
Setup
W-Modbus Compact (840-2130): What do I need before installation?
Also asked as:
- What are the pre-installation requirements?
- What cable should I use for RS485?
- What should I prepare before installing?
Disconnect power, check Modbus RTU requirements (Application Guide) and environment (wireless design). Use shielded twisted-pair RS485 cable with 100–130 Ω impedance. Compact-specific: minimal space is needed, but ensure proper ventilation and allow for the cable bend radius. Follow local codes and use PPE. Do not install the Compact inside a metal cabinet or enclosure: the metal attenuates the wireless signal and drastically reduces range. Mount it outside the cabinet and, if the connected device is inside, run the RS485 cable out to it. See Electrical Cabinets (section ID: electrical-cabinets).
Manual section: Setup Guide > Pre-installation Requirements; Radio planning > Radiation pattern > Compact (section ID: pre-installation-requirements)
See also: Radiation pattern (section ID: radiation-pattern), Wireless best practices (section ID: installation-and-placement-of-wireless-devices-and-external-antennas)
W-Modbus Compact (840-2130): What are the physical installation steps?
Also asked as:
- How do I install the device?
- How do I mount and wire the unit?
- What are the setup steps?
1) Check the unit for damage. 2) Mount the backplate of the enclosure on the wall; it fits onto a junction box. 3) Connect power and the Modbus RTU device, using the rear and/or side knockouts for cable entry. 4) Confirm the wiring is secure and the LEDs light. 5) Secure the front case to the backplate. The Compact takes its bus settings from the gateway, so set the baud rate on the Wall mount or DIN rail gateway (default 9600 baud, no parity, 1 stop bit). Do not install the Compact inside a metal cabinet or enclosure: the metal attenuates the wireless signal and drastically reduces range. Mount it outside the cabinet and, if the connected device is inside, run the RS485 cable out to it. See Electrical Cabinets (section ID: electrical-cabinets).
Manual section: Setup Guide > Physical Setup; Radio planning > Radiation pattern > Compact (section ID: physical-setup)
See also: Radiation pattern (section ID: radiation-pattern), Wireless best practices (section ID: installation-and-placement-of-wireless-devices-and-external-antennas)
W-Modbus Compact (840-2130): Where should I install the Compact? Can it go inside a metal cabinet?
Also asked as:
- Where do I mount the Compact during installation?
- Can I put the Compact in an electrical panel or control cabinet?
- Should the Compact be installed inside or outside the cabinet?
- Does the installation location affect the wireless signal?
- Can I install the unit in a steel or metal enclosure?
Install the Compact outside any metal cabinet or enclosure, ideally in open space with a clear path to neighboring nodes. Do not place it inside a metal cabinet: the metal attenuates the wireless signal and drastically reduces range and link quality. If the connected device sits inside a cabinet, run the RS485 cable out to the Compact. If the unit must be housed inside a metal cabinet, use the DIN rail form factor with an external antenna mounted outside the cabinet. For the best performance, physically install the unit according to the radiation pattern shown in the images in Radio planning > Radiation pattern (section ID: radiation-pattern).
Manual section: Radio planning > Electrical Cabinets (section ID: electrical-cabinets)
W-Modbus Compact (840-2130): Should I commission with the app or without it?
Also asked as:
- Which commissioning method should I use?
- Can I commission without a phone?
- How do I add a node to an existing network?
There are two valid ways to commission a Compact node to a gateway: the mobile app commissioning method and the physical commissioning method (without the app). Both work, but the mobile app method is preferred: it identifies devices, adds nodes and shows the network map. The Compact works only as a node, so the gateway is always a Wall mount or DIN rail unit, and the gateway's three-pole switch sets the network mode (the Compact has no switch). With the app, the gateway stays in secure mode (switch in the secure-gateway position). With the physical method, set the gateway switch to the commissioning position (COMM. on a DIN rail, ◻ on a Wall mount), let the Compact and other nodes join, then switch it back to the secure-gateway position. To add nodes to an existing network, use the app; putting the gateway back into commissioning mode uncommissions all existing nodes.
Manual section: Setup Guide > Commissioning procedure selector (section ID: commissioning-procedure-selector)
W-Modbus Compact (840-2130): How do I commission nodes using the mobile app?
Also asked as:
- How do I add nodes with the app?
- What are the steps for app commissioning?
- How do I join a node to a gateway using my phone?
This is the preferred of the two valid commissioning methods (the other is the physical commissioning method, without the app). The Compact works only as a node, so it joins a Wall mount or DIN rail gateway. Set the gateway's three-pole switch to the secure-gateway position (Gateway on a DIN rail, ◼ on a Wall mount). Triple-press the gateway button, open the app, tap Commission, then identify and select (and optionally rename) the gateway. The Compact ships in commissioning mode (blue sweep); if it doesn't show a blue sweep, hold its button for 10 s to uncommission it. Tap Add on the Compact; it reboots and its first LED turns green, yellow or red to show signal strength. Check the node count and network map afterwards.
Manual section: Mobile App Commissioning Method (Step-by-Step) (section ID: mobile-app-commissioning-method-stepbystep)
W-Modbus Compact (840-2130): How do I commission without the app?
Also asked as:
- How do I commission using the switch?
- How do I set up a network without the mobile app?
- What is the physical commissioning method?
This is the physical commissioning method, one of two valid ways to commission nodes; the other is the mobile app method, which is preferred. The Compact works only as a node and has no switch, so all mode changes are made on the gateway (a Wall mount or DIN rail unit). Set the gateway's three-pole switch to the commissioning position (COMM. on a DIN rail, ◻ on a Wall mount). Power the Compact: it shows a blue sweep in commissioning mode (if not, hold its button for 10 s). The Compact blinks all LEDs green when it receives the network credentials. Confirm all devices in your Modbus RTU client, then set the gateway switch back to the secure-gateway position (Gateway on a DIN rail, ◼ on a Wall mount); the nodes blink yellow and reboot. The network takes up to 15 minutes to reform.
Manual section: Physical Commissioning Method (Step-by-Step) (section ID: physical-commissioning-method-stepbystep)
W-Modbus Compact (840-2130): How do I verify my installation is working?
Also asked as:
- How do I check that the installation works?
- What should I check after commissioning?
- Is there an installation checklist?
Gateway in secure mode with all nodes commissioned (allow up to 15 min to reform); node LEDs green or yellow, and RS485 LEDs green where Modbus RTU devices are expected; all nodes visible in the network map with PDR above 95% (no RS485 hexagon is expected on the gateway); the Modbus RTU client can read the intended Modbus RTU servers; save a network map PDF.
Manual section: Setup Guide > Installation Verification; Radio planning > Radiation pattern > Compact (section ID: installation-verification)
See also: Radiation pattern (section ID: radiation-pattern), Wireless best practices (section ID: installation-and-placement-of-wireless-devices-and-external-antennas)
Application
W-Modbus Compact (840-2130): What are the recommended Modbus RTU client settings?
Also asked as:
- What timeout and retries should my Modbus master use?
- What are the best-practice Modbus settings?
- How long should the Modbus response timeout be?
Use a reply timeout of at least 1 second and at least 3 retries per request, and aim for PDR above 95% on all nodes. W-Modbus typically adds 50–80 ms of latency, but responses can take up to 500 ms depending on the amount of data, the device baud rate and the use of repeaters. If you have more than 25 Modbus RTU devices that need a fast response, split them across several networks. For fast-polling devices such as solar inverters, enable Solar mode.
Manual section: Application Guide > Best practice settings / Response latency (section ID: best-practice-settings)
W-Modbus Compact (840-2130): What is Solar mode and how do I enable it?
Also asked as:
- How do I use W-Modbus with a solar inverter?
- How do I turn on Solar mode?
- Which inverters and smart meters work with Solar mode?
Solar mode improves compatibility with solar inverters that poll very fast (some wait 100 ms or less for a reply). It needs firmware 4.2.0 or later and the latest W-Modbus app. Connect to the gateway in the app and toggle Solar Mode on the home screen; the gateway restarts and all nodes rejoin, causing brief downtime. Connect the inverter at the Gateway and the smart meter at a Node (the Compact can be the smart-meter node; the gateway must be a Wall mount or DIN rail), adding repeater nodes in between if needed. LumenRadio keeps a list of tested inverter and smart meter pairs (including Fronius, Growatt, Huawei, Kostal, SAJ, Sigenergy, Solinteg, Solis and Sungrow) but cannot guarantee compatibility. Where possible, disable automatic firmware updates on the inverter and smart meter, and raise a support ticket for untested combinations.
W-Modbus Compact (840-2130): Can I monitor the wireless network from my Modbus client (remote diagnostics)?
Also asked as:
- Can I read network diagnostics over Modbus?
- Which registers show the wireless network status?
- What address does the gateway use for diagnostics?
Yes, via the gateway (a Wall mount or DIN rail unit); Compact nodes appear in its per-node registers. The gateway also acts as a Modbus RTU server and exposes wireless network diagnostics in holding registers, read with function code 3 (Read Holding Registers) at the default address 201. Remote diagnostics over Modbus is available only from gateway firmware 4.3.0; earlier firmware does not expose these registers, so update the gateway first. The registers must be configured manually in your Modbus client. Key registers: 30 = number of wireless nodes; 31 = number of Modbus server devices; 32–34 = firmware major/minor/patch; 35–36 = nodes that received/installed the latest firmware; 37 = Solar mode enabled; 57 = RSSI to parent; 59–60 = uptime in hours; 101–200 = PDR per node (255 = no valid link); 301–400 = parent node ID (255 = direct link to the gateway); 501–600 = RS485 bus configuration per node; 801–1800 = node names; 2000–3599 = Modbus addresses per node. Register availability depends on the gateway firmware version. On site, connect to the gateway with the W-Modbus mobile app and open the network map: the hexagon next to each node shows its PDR (packet delivery ratio), see Mobile App > Network Map > PDR (section ID: pdr).
Manual section: Remote Diagnostics > Register mapping; Release Notes > 4.3.0 (section ID: remote-diagnostics)
Remote diagnostics
W-Modbus Compact (840-2130): How do I monitor the wireless performance of my W-Modbus network?
Also asked as:
- How do I check the health of the wireless network?
- How can I see the signal quality of each node?
- How do I know if the wireless links are good enough?
There are two ways:
- In the mobile app: connect to the gateway with the W-Modbus mobile app and open the network map. The hexagon next to each node shows its PDR (packet delivery ratio): green ≥ 99%, amber 94–99%, red < 94%. Aim for a PDR above 95% on every node. See Mobile App > Network Map > PDR (section ID: pdr).
- Remotely in your BMS, Niagara, SCADA or other Modbus client: the gateway exposes the wireless network metrics, including per-node PDR, RSSI and link quality, through remote diagnostics. Requires gateway firmware 4.3.0 or later. See Remote Diagnostics (section ID: remote-diagnostics).
Manual section: Mobile App > Network Map > PDR (section ID: pdr); Remote Diagnostics (section ID: remote-diagnostics)
W-Modbus Compact (840-2130): Can I see the wireless diagnostics in Niagara or another BMS?
Also asked as:
- How do I show the wireless network diagnostics in Niagara?
- Are the wireless diagnostics visible remotely in my BMS or SCADA system?
- Can my BMS read the network health, PDR and signal strength of the nodes?
Yes. Any BMS or controller that works as a Modbus RTU client (master), such as Niagara, can read them. The gateway answers on Modbus address 201 and exposes the wireless network metrics as holding registers (function code 0x03). Remote diagnostics over Modbus is available only from gateway firmware 4.3.0; earlier firmware does not expose these registers, so update the gateway first. Add the registers you need to your Modbus client using the register map in the manual. On site, connect to the gateway with the W-Modbus mobile app and open the network map: the hexagon next to each node shows its PDR (packet delivery ratio), see Mobile App > Network Map > PDR (section ID: pdr).
Manual section: Remote Diagnostics (section ID: remote-diagnostics)
Troubleshooting
W-Modbus Compact (840-2130): The RS485 LED is red / no RS-485 device detected. What do I do?
Also asked as:
- Why is my RS485 device not detected?
- The third LED is red – what does it mean?
- Why can't the node find the connected device?
Check RS485 polarity and the bus settings (baud rate, parity, stop bits). Make sure the Modbus RTU client (master) is connected to the W-Modbus Gateway and the servers (slaves) are connected to the nodes. In solar installations, the inverter must be connected at the Gateway and the smart meter at the Node, with the gateway in Solar mode. Confirm the Modbus RTU device itself works.
Manual section: Troubleshooting > No RS-485 device detected (section ID: no-rs-485-device-detected)
W-Modbus Compact (840-2130): How does a node find its Modbus RTU devices, and how long does it take?
Also asked as:
- How long does it take a node to find my Modbus device?
- How does Modbus address scanning work?
- How do I restart the Modbus device scan?
Nodes scan Modbus RTU addresses 1 to 255 using the current baud rate, parity and stop bits, by requesting holding register 0 from each address with a 300 ms timeout. A device at address 255 therefore takes about 1 min 17 s to be found. The third LED blinks faster while scanning and changes from red to green once a device is found. Double-press the button to restart the scan. You can also set device addresses manually in the app.
Manual section: Application Guide > Server Scanning; Mobile App > Setting Modbus Addresses (section ID: server-scanning)
W-Modbus Compact (840-2130): Nodes aren't connecting to the gateway. What should I check?
Also asked as:
- Why won't my node join the gateway?
- A node is missing from the network – what should I check?
- Why is my node blinking yellow?
Check which of the two commissioning methods you are using – both are valid, and the mobile app method is preferred. Remember the Compact is always a node, so all mode settings are on the Wall mount or DIN rail gateway. Mobile app method: confirm the gateway's three-pole switch is in the secure-gateway position (Gateway on a DIN rail, ◼ on a Wall mount) and that you tapped Add for the Compact in the app. Physical method: confirm the gateway switch is in the commissioning position (COMM. on a DIN rail, ◻ on a Wall mount) and the Compact is in commissioning mode (blue sweep). In both cases, check that nothing is still in range test mode and that the Compact is within range; move it closer or add repeater nodes.
Manual section: Troubleshooting > Wireless > Nodes are not connecting (section ID: nodes-are-not-connecting-to-gateway)
W-Modbus Compact (840-2130): Some nodes stay in secure mode after I switched the gateway back to commissioning. Why?
Also asked as:
- Why didn't all nodes return to commissioning mode?
- Some nodes didn't follow the gateway into commissioning mode – what now?
- How do I get all nodes back into commissioning mode?
Those nodes hadn't rejoined the gateway in time to get the instruction. Put the gateway back in secure mode for 10 minutes so all nodes rejoin, then switch to commissioning; or uncommission each node manually (hold button 10 s).
Manual section: Troubleshooting > Wireless (section ID: when-i-put-the-gateway-back-into-commissioning-mode-some-nodes-stay-in-secure-mode)
Firmware
W-Modbus Compact (840-2130): What is the latest firmware and how do I check my version?
Also asked as:
- Which firmware version is the latest?
- How do I check which firmware a device runs?
- How do I read the firmware version from the LEDs?
Latest is 4.3.1 (released 2026-11-18). Check in the app, or hold the button 15 s and release on cyan: the top LED blinks the major number, the middle LED the minor and the bottom LED the patch (e.g., 3-3-2 blinks = 3.3.2).
Manual section: Firmware Updates > Checking Current Version (section ID: checking-current-version)
W-Modbus Compact (840-2130): How do I update firmware without the W-Modbus app?
Also asked as:
- How do I update firmware with nRF Connect?
- Can I update firmware without the W-Modbus app?
- How do I update devices with very old firmware?
The preferred way to update firmware is always through the W-Modbus app. Use the nRF Connect update flow only if the device runs firmware below 3.0.0, or as a fallback after multiple failed update attempts with the W-Modbus app: download the firmware zip from LumenRadio, install nRF Connect, hold the button for 20 s until the middle LED turns red (bootloader mode), scan and connect to the W-Modbus-DFU device, select the file via the DFU icon and wait for "Application has been sent successfully". Below 3.0.0, FOTA is not available, so every device must be updated this way. From 3.0.0 onwards, update only the gateway and FOTA updates the nodes.
Manual section: Firmware Updates > Update Procedures > nRF Connect (section ID: nrf-connect)
W-Modbus Compact (840-2130): What changed in firmware 4.3.0 and are there known issues?
Also asked as:
- What's new in firmware 4.3.0?
- What are the known issues in the latest firmware?
- Where can I find the release notes?
Released 2026-09-07. Added: improved Solar mode compatibility, wireless network diagnostics readable over Modbus RTU, and support for the OEM Module Development Kit MK2. Changed: range test mode exits automatically after 30 minutes. Fixed: failures when fetching network information via the app, and intermittent RS485 communication failures. Known issues: bandwidth is reduced by 33% while the app is connected; downgrading below 3.0.0 factory-resets the device.
Manual section: Firmware Updates > Release Notes > 4.3.0 (section ID: 430)
Support
W-Modbus Compact (840-2130): How long is the warranty and what voids it?
Also asked as:
- What is the warranty period?
- What voids the warranty?
- Is the device covered by warranty?
Warranty length is set by your distributor, typically 1–5 years from shipment. It is void if the product is repaired or modified without LumenRadio approval, or the serial number is missing or illegible. Defects must be reported in writing within 15 days of discovery.
Manual section: Warranty and Support > Warranty Terms / Return and complaint policy (section ID: warranty-terms)
W-Modbus Compact (840-2130): Who should I contact for support and what should I include?
Also asked as:
- How do I contact support?
- What information should I include in a support ticket?
- How do I raise a support ticket?
Contact your installer or distributor first for installation, wiring, power, configuration and warranty questions; contact LumenRadio support for firmware errors (e.g., all LEDs solid red) or unresolved issues via Create Support Ticket. Include symptoms, product/serial/firmware, controller make and model, steps tried, photos, LED video, network map PDF/PDR, power type, bus settings, wireless conditions and antennas used.
Manual section: Warranty and Support > When to Contact Support / What to include (section ID: when-to-contact-support)
W-Modbus Compact (840-2130): How do I file an RMA?
Also asked as:
- How do I return a faulty device?
- How do I make a warranty claim?
- What does an RMA request need to include?
Submit an RMA claim through the LumenRadio support system with the product serial numbers, a clear fault description, and details of how the device was installed.
Manual section: Warranty and Support > RMA claims (section ID: rma-claims)
Regulatory
W-Modbus Compact (840-2130): What certifications does the product have?
Also asked as:
- Is the product CE or FCC certified?
- Which regulatory approvals does it have?
- Which countries is the product certified for?
CE (RED 2014/53/EU), UKCA, FCC Part 15 Class B (FCC IDs XRSTIMOMWAN301, XRSTIMOMWAN201), Industry Canada/ISED, MIC (Japan) and KC (South Korea), with 2.4 GHz approvals listed for China, India, Australia, South Africa, Malaysia and Vietnam. Keep at least 20 cm between antenna and people (FCC exposure).
Manual section: Regulatory Compliance (section ID: regulatory-compliance)
W-Modbus Compact (840-2130): Is the W-Modbus wireless communication encrypted and secure?
Also asked as:
- What encryption does W-Modbus use?
- How is W-Modbus protected against hacking?
- What security features does W-Modbus have?
Yes. All data sent over the W-Modbus wireless mesh is encrypted with AES-128, and only devices with the network credentials can join the mesh. Configuration requires physical access to the device, network keys are only shared as encrypted blobs that only W-Modbus devices can decrypt, and firmware updates are signed and verified on every device.
Manual section: Security features (section ID: security-features)
W-Modbus Compact (840-2130): Can W-Modbus be accessed or managed from the internet?
Also asked as:
- Does W-Modbus have an IP or cloud connection?
- Can someone reach the W-Modbus devices remotely over the network?
- Does W-Modbus support remote management?
No. W-Modbus devices have no Ethernet, Wi-Fi or other interface to an external IP network, no border-router function and no cloud or remote management interface. IPv6 is used only for internal addressing inside the encrypted MiraMesh network. The devices cannot be configured, managed or updated from the internet or over the Modbus interface.
Manual section: Interfaces (section ID: interfaces)
W-Modbus Compact (840-2130): Can someone change the W-Modbus configuration over Bluetooth without physical access?
Also asked as:
- Is Bluetooth always on?
- How is configuration over BLE protected?
- How close do I need to be to connect with the mobile app?
No. W-Modbus devices do not advertise over Bluetooth Low Energy (BLE) by default. Press the button on the device three times to make it connectable; it then advertises for 3 minutes and stops if no connection is made. A connected session disconnects automatically after 2 minutes of inactivity. The BLE connection uses only the on-chip antenna, so you normally need to be within 2–3 m of the device.
Manual section: Configuration requires physical access (section ID: configuration-requires-physical-access)
W-Modbus Compact (840-2130): How are W-Modbus firmware updates protected?
Also asked as:
- Are firmware updates signed?
- Can someone install malicious firmware on W-Modbus?
- How do I know a firmware update is genuine?
Every firmware file is digitally signed. The update is sent from the mobile app over BLE to the gateway, which distributes it to the nodes as AES-128-encrypted mesh messages. The gateway and each node check the signature before installing; if the check fails, that device rejects the update and keeps its current firmware. Updates can only start over BLE, so they need physical access to the gateway.
Manual section: Secure firmware updates (section ID: secure-firmware-updates)
W-Modbus Compact (840-2130): Does W-Modbus comply with the RED cybersecurity requirements (EN 18031)?
Also asked as:
- Is W-Modbus in scope of RED Article 3(3)(d), (e) or (f)?
- Does W-Modbus need EN 18031-1 certification?
- What about Delegated Regulation (EU) 2022/30?
LumenRadio has assessed W-Modbus as outside the scope of RED Article 3(3)(d), because it has no interface to any external IP network and cannot communicate over the internet, so no Notified Body evaluation against EN 18031-1 is required. Article 3(3)(e) does not apply because W-Modbus does not process personal data, and Article 3(3)(f) does not apply because it has no financial functions. W-Modbus still includes security measures in line with the intent of EN 18031-1.
Manual section: EU Radio Equipment Directive – Article 3(3)(d), (e), (f) (section ID: eu-radio-equipment-directive-article-33d-e-f)
W-Modbus Compact (840-2130): What is the system integrator responsible for to keep a W-Modbus installation secure?
Also asked as:
- How do I secure my W-Modbus installation?
- What security best practices should I follow?
- Who is responsible for network security on the IP side?
Secure the Modbus master (BMS, SCADA system or controller) with access control, strong passwords and up-to-date software; install the devices where unauthorized people can't easily reach them, such as locked cabinets or plant rooms; keep the firmware up to date through the mobile app; and treat Modbus as unauthenticated by restricting who and what can reach the Modbus master.
Manual section: Responsibilities of the system integrator (section ID: responsibilities-of-the-system-integrator)
W-Modbus Compact (840-2130): How do I report a security vulnerability in W-Modbus?
Also asked as:
- Where can I report a security issue?
- Who do I contact about a cybersecurity problem?
- Does LumenRadio have a vulnerability disclosure process?
Submit a request through the LumenRadio support portal. Include the product name, firmware version and a description of the issue, and do not disclose the vulnerability publicly until LumenRadio has had the chance to investigate and respond.
Manual section: Reporting security issues (section ID: reporting-security-issues)